EasyManua.ls Logo

GW Instek PSW Series - Page 168

GW Instek PSW Series
184 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PSW Series User Manual
168
Protection Function
Over voltage protection
(OVP)
Setting range
V
3-33
8-88
16-176
20-275
20-880
Setting accuracy
± (2% of rated output voltage)
Over current protection
(OCP)
Setting range
A
5-79.2
2.7-
29.7
1.44-
15.84
0.9-9.9
0.288-
3.168
Setting accuracy
± (2% of rated output current)
Over temperature protection
(OTP)
Operation
Turn the output off.
Low AC input protection
(AC-FAIL)
Operation
Turn the output off.
Power limit (POWER LIMIT)
Operation
Over power limit.
Value (fixed)
Approx. 105% of rated output power
Analog Programming and Monitoring
External voltage control
output voltage
Accuracy and linearity: ±0.5% of rated
output voltage.
External voltage control
output current
Accuracy and linearity: ±1% of rated output
current.
External resistor control
output voltage
Accuracy and linearity: ±1.5% of rated
output voltage.
External resistor control
output current
Accuracy and linearity: ±1.5% of rated
output current.
Output voltage monitor
Accuracy
%
±1
±1
±1
±2
±2
Output current monitor
Accuracy
%
±1
±1
±1
±2
±2
Shutdown control
Turns the output off with a LOW (0V to
0.5V) or short-circuit.
Output on/off control
Possible logic selections:
Turn the output on using a LOW (0V to
0.5V) or short-circuit, turn the output off
using a HIGH (4.5V to 5V) or open-circuit.
Turn the output on using a HIGH (4.5V to
5V) or open-circuit, turn the output off
using a LOW (0V to 0.5V) or short-circuit.
CV/CC/ALM/PWR ON/OUT
ON indicator
Photocoupler open collector output;
Maximum voltage 30V, maximum sink
current 8mA.