4.2.2 BSB settings
Submenu “BSB settings” is only accessible, if the BSB sensors F5(1-4) and the outside sensor are installed.
BSB without the outside sensor calculates the fuel amount solely based on the available load capacity – therefore the
submenu “BSB settings” is not displayed — no adjustments required.
*only displayed in operating status “Boiler OFF“
5.04 BSB with heating d. YES
Possible settings: “YES” / “NO”.
YES: Fuel calculation considers heating demand and the load capacity.
NO: Fuel calculation only considers the load capacity.
5.05 ABO NO
ABO is not available for all boiler types (see chapter 1.15).
Possible settings: “YES” / “NO”.
YES: Fuel calculation includes modulating operation.
NO: Fuel calculation is carried out for a burning cycle with boiler rated power.
5.06 HC reduced from 22:00
5.06 HC reduced to 06:00
Applies to Logotherm - and externally controlled heating circuits.
BSB assumes, that there is no heating demand during the set reduction time.
Note: If the same time is put at HC reduced from - to, the heating time is deleted.
5.07 TA-design -12°C Setting range: -20°C – +10°C
Required temperature: the value to be adjusted is listed in the heat demand calculation.
5.08 PH-design 0kW Setting range: 0kW – 200kW
Heating demand (“PH”) in kW: the value to be adjusted is listed in the heat demand calculation.