4.2.2 BSB settings
Submenu “BSB settings is only accessible, if the BSB sensors F5(1-4) and the outside sensor are installed.
BSB without the outside sensor calculates the fuel amount solely based on the available load capacity therefore the
submenu “BSB settings” is not displayed no adjustments required.
Selection
Wood Boiler
Wood boiler
Information
Settings
Settings
Chimney sweep
Wood settings
Calibrate O
2
*
BSB settings
BSB settings
Aggregate test*
Display
5.04 BSB with heating d.
NO
Fact.: YES
Initial settings
5.05 ABO
Fact.: NO
YES
5.06 HC reduced from
Fact.: 22:00
5.06 HC reduced to
Fact.: 06:00
5.07 TA-design
Fact.: -12°C
5.08 PH-design
Fact.: 0kW
Call up Selection menu
▲▼ Select Wood Boiler
Confirm selection
Leave menu
▲▼ Select Settings
Confirm selection
Leave menu
▲▼ Select BSB settings
Confirm selection
Leave menu
▲▼ Select menu item
Confirm selection
▲▼ Change value
Confirm value
Leave menu
*only displayed in operating status “Boiler OFF“
5.04 BSB with heating d. YES
Possible settings: “YES” / “NO”.
YES: Fuel calculation considers heating demand and the load capacity.
NO: Fuel calculation only considers the load capacity.
5.05 ABO NO
ABO is not available for all boiler types (see chapter 1.15).
Possible settings: “YES” / “NO”.
YES: Fuel calculation includes modulating operation.
NO: Fuel calculation is carried out for a burning cycle with boiler rated power.
5.06 HC reduced from 22:00
5.06 HC reduced to 06:00
Applies to Logotherm - and externally controlled heating circuits.
BSB assumes, that there is no heating demand during the set reduction time.
Note: If the same time is put at HC reduced from - to, the heating time is deleted.
5.07 TA-design -12°C Setting range: -20°C +10°C
Required temperature: the value to be adjusted is listed in the heat demand calculation.
5.08 PH-design 0kW Setting range: 0kW 200kW
Heating demand (“PH”) in kW: the value to be adjusted is listed in the heat demand calculation.