HDG Lambda-Control 1 plus - ST8: Accumulator Sensor (F4) und Fuel Calculation (BSB) F5-1 - F5-4 (2-Wire Termination); ST9: Water Shortage Fuse (WMS); ST22: Optional Output 3 (WA3): Oil;Gas Boiler (Integrated in Safety Chain); ST22: Optional Output 3 (WA3): Oil;Gas Boiler (Not Integrated in Safety Chain)

HDG Lambda-Control 1 plus
84 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
76
ST8: Accumulator sensor (F4) und Fuel calculation (BSB) F5-1 F5-4 (2-Wire termination)
2-Wire termination for F5-1 F5-4 (Wiring on accumulator)
ST9: Water shortage fuse (WMS)
ST22: Optional output 3 (WA3): Oil/Gas boiler (integrated in safety chain)
ST22: Optional output 3 (WA3): Oil/Gas boiler (not integrated in safety chain)
KL1:
KL2:
Water shortage fuse (WMS)
Remark: If the water shortage fuse (WMS) is enabled, the
contact opens. If there is no water shortage fuse, a wire
bridge must be mounted between KL1 and KL2.
KL1:
KL2:
KL3:
KL4: Free
KL5:
KL6:
KL7:
T = 0°C R = 2000.0
T = 20°C R = 2155.9
T = 80°C R = 2617.9
Accumulator sensor
PF (F4)
Free
Position F4: Upper accumulator
The order of the positioning of F5-1 to
F5-4 in the accumulator is not
important, as an average temperature
value is calculated.
The sensors F4 and F5 (1-4) have to be
positioned in 20% steps spread over
the entire accumulator height.
Sensor types: UF2000 / UFL2000
Advantage: Only 2-pin wire to the plug
board.
Terminals within the dashed lines
marked part are not used with sensor
set BSB2000.
Fuel calc.
(BSB) F5(1-4)
Please note: Optional output WA3 can be loaded with a
power of Imax=5A.
If a higher power is required, a contactor or auxiliary relay
must be used.
A safety temperature limiter (STB) must be installed in
the oil/gas boiler. A boiler thermostat is not necessary
because Lambda-Control 1
plus
is EN14597 (DIN3440)
certified.
Please use only an adaptable cable with a conductor
cross-section of 0.75 mm
2
.
KL1: Free
KL2: PE- Oil/Gas boiler (if required)
KL3: L´- Oil/Gas boiler therm. safety chain
KL4: L- Oil/Gas boiler therm. safety chain
KL5: Free
KL6: Free
L´
PE
L
PE
AK
WK
Please note: The option output WA3 may be loaded with
a power of Imax=5A.
If a higher power is required, a contactor or an auxiliary
relay must be used. However, KL5 cannot be connected;
i.e. only connect a bridge between KL4 and KL6.
A safety temperature limiter (STB) and a boiler
thermostat must be inserted in the oil/gas boiler.
Important note: Because of the contact protection circuit
(RC) the output is not even free of voltage when WA3
(relay contact AK-WK open) is switched off.
Please only use an adaptable cable with a cross-section of
0.75 mm
2
.
KL1: N-Oil/Gas boiler
KL2: PE-Oil/Gas boiler
KL3: L-Oil-/Gas boiler
KL4: WK: Phase input about RC
KL5: RC: RC-Contact protective circuit
KL6: L-Si-Option output 3
(The phase is fused by the fuse Si1
with 6.3A M at the plug board)
N
PE
L
PE
AK
WK
N
RC
L-Si