ST8: Accumulator sensor (F4) und Fuel calculation (BSB) F5-1 — F5-4 (2-Wire termination)
2-Wire termination for F5-1 — F5-4 (Wiring on accumulator)
ST9: Water shortage fuse (WMS)
ST22: Optional output 3 (WA3): Oil/Gas boiler (integrated in safety chain)
ST22: Optional output 3 (WA3): Oil/Gas boiler (not integrated in safety chain)
Water shortage fuse (WMS)
Remark: If the water shortage fuse (WMS) is enabled, the
contact opens. If there is no water shortage fuse, a wire
bridge must be mounted between KL1 and KL2.
KL1:
KL2:
KL3:
KL4: Free
KL5:
KL6:
KL7:
T = 0°C R = 2000.0Ω
T = 20°C R = 2155.9Ω
T = 80°C R = 2617.9Ω
Accumulator sensor
PF (F4)
Position F4: Upper accumulator
The order of the positioning of F5-1 to
F5-4 in the accumulator is not
important, as an average temperature
value is calculated.
The sensors F4 and F5 (1-4) have to be
positioned in 20% steps spread over
the entire accumulator height.
Sensor types: UF2000 / UFL2000
Advantage: Only 2-pin wire to the plug
board.
Terminals within the dashed lines
marked part are not used with sensor
set BSB2000.
Please note: Optional output WA3 can be loaded with a
power of Imax=5A.
If a higher power is required, a contactor or auxiliary relay
must be used.
A safety temperature limiter (STB) must be installed in
the oil/gas boiler. A boiler thermostat is not necessary
because Lambda-Control 1
plus
is EN14597 (DIN3440)
certified.
Please use only an adaptable cable with a conductor
cross-section of 0.75 mm
2
.
KL1: Free
KL2: PE- Oil/Gas boiler (if required)
KL3: L´- Oil/Gas boiler therm. safety chain
KL4: L- Oil/Gas boiler therm. safety chain
KL5: Free
KL6: Free
Please note: The option output WA3 may be loaded with
a power of Imax=5A.
If a higher power is required, a contactor or an auxiliary
relay must be used. However, KL5 cannot be connected;
i.e. only connect a bridge between KL4 and KL6.
A safety temperature limiter (STB) and a boiler
thermostat must be inserted in the oil/gas boiler.
Important note: Because of the contact protection circuit
(RC) the output is not even free of voltage when WA3
(relay contact AK-WK open) is switched off.
Please only use an adaptable cable with a cross-section of
0.75 mm
2
.
KL1: N-Oil/Gas boiler
KL2: PE-Oil/Gas boiler
KL3: L-Oil-/Gas boiler
KL4: WK: Phase input about RC
KL5: RC: RC-Contact protective circuit
KL6: L-Si-Option output 3
(The phase is fused by the fuse Si1
with 6.3A M at the plug board)