64
LambdaControl 1
Error 26.54
Acc. sensor F4
from Bus
Cause: Bus-Communication, Different number of accumulator sensor
Display 4 amber: illuminates
Information text: -
Emergency program: YES
Reset: Automatically after error correction
Cause of error: There is a wrong accumulator sensor No. set in the Lambda-Control 1
plus
. Are both CAN-bus plugs properly
pressed on to the CAN-bus cable?
Rectification: Call service technician possible causes:
1. Test is the correct accumulator sensor number set in the controller Lambda-Control 1
plus
? Is that the case, continue
with test 2.
2. Test CAN-Bus cable: Are both CAN-bus plugs properly pressed on to the CAN-bus cable and is the cable properly
connected to the CAN bus terminal ( check the correct pin assignment)?
Experience shows that the controller is usually only defective, if faulty wiring or spurious actions damaged the applicable
input/output.
Controller function: Combustion without BSB.
Error 26.55: BSB F5(1 4) from BUS
LambdaControl 1
Error 26.55
BSB F5(1-4)
from Bus
Cause: Bus-Communication, Different number of accumulator sensor
Display 4 amber: illuminates
Information text: -
Emergency program: YES
Reset: Automatically after error correction
Cause of error: There is a wrong accumulator sensor No. set in the Lambda-Control 1
plus
. Are both CAN-bus plugs properly
pressed on to the CAN-bus cable?
Rectification: Call service technician possible causes:
1. Test is the correct accumulator sensor No. set in the Lambda-Control 1
plus
? Is that the case, continue with test 2.
The BSB F5(1-4) Sensor is interconnected with the accumulator sensor No.
2. Test CAN-Bus cable: Are both CAN-bus plugs properly pressed on to the CAN-bus cable and is the cable properly
connected with the CAN bus terminal ( check the correct pin assignment)?
Experience shows that the controller is usually only defective, if faulty wiring or spurious actions damaged the applicable
input/output.
Controller function: Fuel calculation is not carried out.
11 TÜV: Tests and engineering standards
The controller Lambda-Control 1
plus
is based on the hardware of the controller Lambda-Control 2
plus
which was tested
by TÜV following these norms:
Safety temperature limiter (STB):
DIN EN14597 Register number: STB/FR/TR 1188
DIN EN 60730-2-9
DIN EN 60730-1
DIN EN 298
VdTÜV- data sheet Temperature 100
Temperature and firing controller:
DIN EN14597 Register number: STB/FR/TR 1188
EMC interference emission:
DIN EN61000-6-3
DIN EN61000-6-4
DIN EN61000-3-2
EMC interference emission resistance:
DIN EN61000-6-1
DIN EN61000-6-2
Electrical safety:
DIN EN60335 / VDE0700-1
VDE0722