16
2.3 Technician password
The submenu “Password” is located in the “Selection” menu; it contains:
Password
In “Password” after pressing button a random number is
displayed, which needs to be changed and confirmed by the
Technician.
The display “Technician” indicates successful code entering.
The display “No password” indicates that the enabling of the
required settings is locked.
Password ---
Technician/No Password
Enter password
▲▼ Change password
Confirm settings
After entering the password, the “Commissioning” menu is displayed.
If the system has been commissioned already, the settings requiring a password are enabled
in the menus.
Settings requiring a password are marked in this colour.
Settings that do not require a password are marked in this colour.
2.4 Commissioning settings
Button functions:
▲▼ Change value / Confirm value, then the next setting is displayed.
In case of wrong settings being confirmed, they may be corrected after commissioning (see chapter. 2.5).
Language English [EN]
Language to be selected: DE, EN, FR, IT,…
Heating sys. No. ---
Be mindful of the right setting.
B-Type ---
Boiler type (check the type label).
Boiler new YES
This position only appears, if the value of total fire hours (“Boiler t.“, see “Operations counter“ in chapter 4.1.2) is 0 hrs.
Possible settings: “YES” / “NO”.
YES: If the flue gas temperature requires correction due to the “missing natural emission” during the
initial 50 hours.
NO: In case of a new controller and a boiler that has been in use before.
Flue gas min. ---°C
Setting range: Determined by the adjusted boiler range (see chapter 1.16).
The minimum flue gas temperature for the chimney may be increased.
Outside sensor NO (optional)
Possible settings: YES“ / “NO / “BUS“.
YES: If the sensor is installed at the Lambda-Control 1
plus
.
BUS: If the temperature of the sensor is requested over the CAN-bus.
In setting "NO", only the current refuel amount is displayed in correlation with the sensor F5.
Outside sensor No. 1
Possible settings: “1“ / “2“ / “3“ / “4“ .
This setting is important if the sensor is required for other Logotherm control devices.
DCF77-receiver NO
Possible settings: YES“ / “NO.
YES: If the receiver is installed, it serves for the automatic data- and time setting.
Depending on the region receiving DCF signal might not be possible.
Time zone GMT+1 Setting range: -1 to +3
Note: The setting is only shown, if DCF77-Receiver YES was selected.
+1: Setting for AT, DE, IT, FR, DK, SE and other countries in this time zone.
Acc. sensor F4 YES
Possible settings: YES“ / “BUS“.
YES: If the sensor is installed at the Lambda-Control 1
plus
.
BUS: If the temperature of the sensor is requested over the CAN-bus.