10 Errors - Notes
In case of errors or notes, follow the indicated error or note number in the text display. Each error
and note is described in the following chapter.
If the red display 3 illuminates: Wood boiler or controller operation is not possible. This is also
shown on the remote control panel or remote indication (LED) by flashing in one-second intervals.
If the “amberdisplay 4 illuminates: Wood boiler operation is possible with an automatically
started emergency program. This is indicated on the remote control panel or remote indication
(LED) by flashing in one-second intervals.
Notes: They are indicated by the amber” flashing indicator 4 until a new burning cycle is initiated
for information purposes only.
Information: Indicated by the amber indicator until a new burning cycle is initiated or the
information is not required anymore (e.g. flue gas temperature too high, please wait, etc.).
Emergency programs: They are automatically executed and to serve the short-term maintenance
of the heating operation.
We recommend rectifying errors as soon as possible.
A technician might be necessary for error correction follow the point “Rectification” in the
respective malfunction description.
Tampering with the electric system, can be extremely dangerous and can result in significant
damages.
Operating the system with an emergency program for too long may damage the boiler and the chimney which can
void the warranty. All errors and notes for each burning cycle are recorded in the controller and can be reviewed by the
manufacturer.
The manufacturer can review all recorded errors and notes.
Note 1.16: Protective functions
LambdaControl 1
Note 1.16
Protective functions
Cause: -
Display: -
Information text: -
Emergency program: -
Reset: -
Pump and valve stuck protection: They are operated in a 7-day rhythm, i.e. every Sunday the stuck protection starts at 3.00
o'clock. For that purpose the wood boiler has to be in operating status “OFF for at least one hour and the boiler temperature has
to be under 60°C. The Pellet/Oil/Gas boiler (if installed) must be in operating status OFF with a temperature under 60°C.
Error 1.17: EW-1 HC BUS-Communication
LambdaControl 1
Error 1.17
Ext.-1 HC
BUS-Communication
Cause: Bus-Communication, EW-Module No. on the controller and the EW- Module
do not match, CAN-Bus cable defective
Display 4 amber: illuminates
Information text: -
Emergency program: -
Reset: Automatically after error correction
Error detection There is a different Bus-No. set in the EW-Module than in the controller Lambda-Control 1
plus
. Check the setting in
30.48 Ext.-1 HC ”NO / YES“ in chapter 2.5. Are both CAN-bus plugs pressed properly on to the CAN-bus cable?
Rectification: Adjust the EW-module bus numbers to each other, repress CAN-bus plugs or inform technician.
Error 1.18: EW-ignition BUS-Communication
LambdaControl 1
Error 1.17
EW-ignition
BUS-Communication
Cause: Bus-Communication, EW-Module No. on the controller and the EW- Module
do not match, CAN-Bus cable defective
Display 4 amber: illuminates
Information text: -
Emergency program: -
Reset: Automatically after error correction
Error detection: There is a different Bus-No. set in the EW-Module than in the controller Lambda-Control 1
plus
. Check the setting in
30.50 EW-ignition NO / YES“ in chapter 2.5. Are both CAN-bus plugs pressed properly on to the CAN-bus cable?
Rectification: Adjust the EW-module bus numbers to each other, repress CAN-bus plugs or inform technician.