33
5.23 Service small NO
Possible settings: “NO” / YES”.
NO: The function Service small is deactivated.
YES: The function “Service small” is activated (see chapter 3.5).
4.3 Chimney sweep test
This submenu is only displayed in operating status “Boiler ON”.
The test is selected via “Select” → “Wood Boiler” →Chimney sweep” →…(particular test step) and comprises three test
steps: “Rated Power” / “Smallest output” / “Safety test”. The test steps “Rated power” and “Smallest output” are only
present and are only selectable, if function AFO (see chapter 1.4) is completed.
Test programs
Function
Chimney sweep:
Rated power (PK
N
)
Setting: Select Rated power
Function: Controller to PK
N
Type.
Note: - All safety-relevant functions are activated.
- Test ends automatically after 30 minutes or can be ended by leaving the menu
a “Chimney sweep.
Chimney sweep:
Smallest output
(PK min.)
Setting: Select Smallest output
Function: Depending on the characteristics of the fuel and the setting 5.13 Flue gas min. the
a controller runs down to the smallest boiler output.
Note: - All safety-relevant functions are activated.
- Test ends automatically after 30 minutes or can be ended by leaving the menu
a “Chimney sweep.
Chimney sweep:
Safety test (PK
N
)
STB-test and test of
thermal safety
device
Setting: Select Safety test
During the test the button needs to be held pressed or at least be pressed
a every 30 seconds. The timer status is displayed.
Function: Controller switches to PK
N
Type until STB triggers.
Primary pump M1 OFF / Return valve Y1 CLOSED.
If the boiler temperature rises above 97.5°C ± 2.5K, STB must trigger and
deactivate the fan.
At the same time the display shows “Error 26.08 STB triggered”. If STB triggered,
the STB test was completed successfully.
If the button is still pressed after triggering STB, the primary pump M1
remains OFF up to 110°C and Y1 remains closed to test the thermal safety
s device.
The thermal safety device must now be able to keep the boiler temperature
below 110°. Is that the case, the test of the thermal safety device is completed
m successfully.
Automatic test interruption, if:
Boiler temp. ≥ 110°C
30sec timer elapsed
Test duration exceeded 30 minutes.
Function after test cancellation: Fan OFF, M1 ON, Y1 OPEN.
Reset STB: Unscrew STB cap, press STB reset button, if the temperature dropped below 86°C.
After a successful STB test, be boiler must be switched ON by pressing the button.