4.2.4 Initial settings
Selection
Wood Boiler
Wood Boiler
Information
Settings
Settings
Chimney sweep
Wood settings
Calibrate O
2
*
BSB settings
Aggregate test*
Display
Initial settings
Initial settings
5.11 Boiler set control
Fact.: automatic
manual
5.12 Boiler set**
Fact.: 80.0°C
5.13 Flue gas min. ---°C
Fact.: smallest
Boiler output
5.14 Switch-off
Fact.: O
2
TAG
5.15 Runtime Y1
Fact.: 150sec
5.16 Runtime Y2
Fact.: 150sec
5.17 AF. extended***
Fact.: NO
YES
5.21 RWO
Fact.: Acc.-F4
Acc.-BSB (F5)
OFF
5.22 Y2 Enabling
Fact.: 90°C
5.23 Service small
Fact.: NO
YES
Call up Selection menu
▲▼ Select Wood Boiler
Confirm selection
Leave menu
▲▼ Select Settings
Confirm selection
Leave menu
▲▼ Select Initial settings
Confirm selection
Leave menu
▲▼ Select menu item
Confirm selection
▲▼ Change value
Confirm value
Leave menu
*only displayed in operating status “Boiler OFF“ **only displayed if the setting in 5.11 Boiler set control is “manual
**only displayed if the setting in 10.06 Outside sensor is “YES”
5.11 Boiler set control automatic
Control mode of the set boiler temperature.
Possible settings: “automatic” / “manual”.
automatic: Maximum use of fuel chamber and accumulator capacity.
manual: The controller operates according to the value set manually in position 5.12 Boiler set (primarily
for special applications, i.e. technical heat).
Note: The boiler output is only reduced if the boiler temperature exeeds 89°C.
5.12 Boiler set 80.0°C
Set boiler temperature.
The minimum and maximum value are determined by the manufacturer.
Note: The boiler output is only reduced if the boiler temperature exceeds 89°C. The set return flow value
is regulated according to the set boiler temperature.
5.13 Flue gas min. ---°C Setting range: 90°C 228°C
Minimum flue gas temperature.
Setting range: Defined by the set boiler type (chapter 1.16).
The flue gas temperature may be increased.