*only displayed in operating status “Boiler OFF“ **only displayed if the setting in 5.11 Boiler set control is “manual”
**only displayed if the setting in 10.06 Outside sensor is “YES”
5.11 Boiler set control automatic
Control mode of the set boiler temperature.
Possible settings: “automatic” / “manual”.
automatic: Maximum use of fuel chamber and accumulator capacity.
manual: The controller operates according to the value set manually in position 5.12 Boiler set (primarily
for special applications, i.e. technical heat).
Note: The boiler output is only reduced if the boiler temperature exeeds 89°C.
5.12 Boiler set 80.0°C
Set boiler temperature.
The minimum and maximum value are determined by the manufacturer.
Note: The boiler output is only reduced if the boiler temperature exceeds 89°C. The set return flow value
is regulated according to the set boiler temperature.
5.13 Flue gas min. ---°C Setting range: 90°C – 228°C
Minimum flue gas temperature.
Setting range: Defined by the set boiler type (chapter 1.16).
The flue gas temperature may be increased.