20.02 Lock time from 00:00
20.02 Lock time to 00:00
The period in which the burner is switched off, except for an Anti-freeze request.
In order to delete the lock time, set the same time for from – to.
20.03 Base temp. 40°C Setting range: 8°C – 80°C
Base temperature. Can be required in the accumulator to ensure the hot water supply and/or if there are externally
controlled heating circuits.
If the temperature drops below the set value and pellet/oil/gas enabling is active, and Acc. t.-F4 ≤ 20.06 Enabling, then
the burner is switched on.
Burner ON: If "Acc. t.-F4" is smaller than 20.03 Base temp.
Burner OFF: If "Acc. t.-F4" reaches the in 20.03 Base temp. set value plus 5K and the set 20.05 Min runtime has
elapsed.
20.05 Min. runtime 30min Setting range: 2min – 240min
Minimum runtime (Enabling) of the pellet/oil/gas burner in minutes.
20.06 Enabling 42°C Setting range: 8°C – 80°C
The pellet/oil/gas enabling is only carried out, if "Acc. t.-F4" ≤ 20.06 Enabling. Then the burner operates in the assigned
operation mode and function. If the pellet/oil/gas enabling is carried out Öl-Gas displays.
In the event of the temperature dropping below the set 20.03 Base temp. or there is a request
from an extension module or a Multi-Control 2
plus
, the release is implemented.
By pressing the ► (Recharge) button Enabling is ended.
20.08 !Boiler max. 85°C Setting range: 70°C – 90°C
A maximum boiler temperature can be set; i.e. 85°C is set, the boiler operates until an accumulator temperature – F4 of
83°C is reached. (20.08 !Boiler max. – 2K).
It is recommended that this parameter is adapted to the max. boiler temperature set in the .
Pellet/Oil/Gas thermostat to avoid a too frequent switching on and off of the Pellet/Oil/Gas
boiler.