49
The whole system is regulated to the anti-freeze temperature (Logotherm controlled heating
circuits to anti-freeze, hot water to standard anti-freeze).
Either Anti-freeze, Holiday or reduced has to be chosen as setting while in operation mode
“Boiler OFF” this should be done before firing this way the fuel amount is calculated
without heating demand.
9.3 Summer operation
Selection
General function for heating
circuits, hot water and
E-load circuit.
Sys. operation mode
Sys. operation mode
Operation mode
Holiday
Summer operation
Summer operation
from [mm.dd] --.--
to [mm.dd] --.--
Del. summer op. NO
YES
Call up Selection menu
▲▼ Select Sys. operation mode
Confirm selection
Leave menu
▲▼ Select Summer operation
Confirm selection
Leave menu
▲▼ Select menu item
Confirm selection
▲▼ Change value
Confirm value
Leave menu
Function for Logotherm controlled heating circuit:
Is summer operation selected, the heating circuits are regulated to Anti-freeze.
Function for Logotherm controlled hot water:
The summer operation is overlaid with the selected operation mode; i.e.: If the operation
mode is “ON and the summer operation is set (from, e.g., 03.01 to 10.01), you receive the
following HW charging: In the set time from 1
st
March to 1
st
October the HW tank is only
charged up to HW min + 2K. Is the temperature lower than the in 12.04 HW min. set value, it
is charged again to HW min + 2K. Outside this time, the HW tank is charged to the 12.03 HW
max. value, if the temperature is lower than the value set in 12.04 HW min.
If a “Lock time HW min.” is set in addition to the summer operation, you receive the following
HW charging: In the set time from 1st March to 1st October the HW tank is only charged to
HW min + 2K. During the lock time it is only heated to HW min. +2K; i.e. 12.07 Lock time from
8:00 to 18:00. Outside the set lock time, in “Winter operation”, the hot water is heated to
the in 12.03 HW max. set temperature.
Function for Logotherm controlled E-load circuit:
The summer operation is overlaid with the selected operation mode; i.e.: If the operation
mode is set on “ON” and the summer operation is set (from, e.g., 03.01 to 10.01), you receive
the following E-circuit charge: In the set time from 1st March to 1st October the HW
tank/accumulator is charged only to E min + 1K. If the temperature falls under the in 18.03 E
min. set value, it is charged again to E min + 1K. Outside this time the HW tank/accumulator is
heated up to the in 18.04 E max. Set value, if the temperature falls under 18.03 E min.
Use: This setting prevents that the hot-water tank is charged to HW max. by a Logotherm regulated
heat generator, in order to supply enough storage capacity for the solar system. Thereby it can be
used more efficiently.
Summer operation
from [mm.tt] --.--
to [mm.tt] --.--
Del. summer op. NO
YES
Month/Day
from: The date on which the summer operation begins
to: The date on which the summer operation ends
Delete summer operation:
YES: Set summer operation is deleted.