10.2 Basic Specifications
190
10.2 Basic Specifications
1. Power Measurement Input Specifications
Measurement line type Single-phase 2-wire (1P2W), Single-phase 3-wire (1P3W), 3-phase 3-wire (3P3W2M, 3P3W3M),
3-phase 4-wire (3P4W)
Number of input channels Voltage: 4 channels U1 to U4
Current: 4 channels I1 to I4
Measurement input terminal
type
Voltage: Plug-in jacks (safety terminal)
Current: Dedicated custom connectors (ME15W)
Input methods Voltage: Isolated inputs, resistive dividers
Current: Isolated input through current sensors (voltage output)
Voltage range 15 V/30 V/60 V/150 V/300 V/600 V/1500 V, selectable for each measured wiring system
Current range When not using the CT9920 Conversion Cable: Sensor rating is automatically detected.
2 A/4 A/8 A/20 A (with the 9272-05, 20 A)
0.4 A/0.8 A/2 A/4 A/8 A/20 A (with the CT6841-05)
4 A/8 A/20 A/40 A/80 A/200 A (200 A sensor)
40 A/80 A/200 A/400 A/800 A/2 kA (2000 A sensor)
0.1 A/0.2 A/0.5 A/1 A/2 A/5 A (5 A sensor)
1 A/2 A/5 A/10 A/20 A/50 A (50 A sensor)
10 A/20 A/50 A/100 A/200 A/500 A (500 A sensor)
20 A/40 A/100 A/200 A/400 A/1 kA (1000 A sensor)
When using the CT9920 Conversion Cable: User must select sensor output rate or sensor model.
400 A/800 A/2 kA (CT7642 and CT7742)
400 A/800 A/2 kA/4 kA/8 kA (CT7044, CT7045, and CT7046)
400 A/800 A/2 kA/4 kA/8 kA/20 kA (100 V/A)
40 A/80 A/200 A/400 A/800 A/2 kA (1 mV/A)
4 A/8 A/20 A/40 A/80 A/200 A (10 mV/A)
0.4 A/0.8 A/2 A/4 A/8 A/20 A (100 mV/A)
Selectable for each measurement channel (however, the same sensor type must be used for each of
the same wire connection channels)
Crest factor 300 (relative to minimum effective voltage/current input) (for 1500 V range: 133)
3 (relative to voltage/current range rating) (for 1500 V range: 133)
Input resistance (50 Hz/60 Hz) Voltage input section: 2 M±40 k (differential input and isolated input)
Current sensor input section: 1 M
±50 k
Maximum input voltage Voltage input section: 1500 V, ±2000 V peak
Current sensor input section: 5 V, ±10 V peak
Maximum rated voltage to
earth
Voltage input terminal 1000 V (50 Hz/60 Hz)
Measurement categories III 600 V (anticipated transient overvoltage 6000 V)
Measurement categories II 1000 V (anticipated transient overvoltage 6000 V)
Measurement method Simultaneous digital sampling of voltage and current, synchronous zero-crossing calculation method
Sampling 500 kHz/16 bit
Measurement frequency range DC, 0.5 Hz to 200 kHz
Synchronization frequency
range
0.5 Hz to 5 kHz
Selectable lower limit measurement frequency (0.5 Hz/1 Hz/2 Hz/5 Hz/10 Hz/20 Hz)
Synchronization source U1 to U4, I1 to I4, Ext (with the motor evaluation installed model and CH B set for pulse input),
DC (50 ms or 100 ms fixed)
Selectable for each measurement channel (U/I for each channel measured using the same synchroni-
zation source)
The zero-crossing filter automatically follows due to the digital LPF when U or I is selected.
Two filter levels for zero-crossing filter (strong or mild)
Operation and accuracy are undetermined when the zero-crossing filter is disabled (off).
Operation and accuracy are undetermined when U or I is selected and measured input is below 30% f.s.
CH1 CH2 CH3 CH4
Pattern 1 1P2W 1P2W 1P2W 1P2W
Pattern 2 1P3W 1P2W 1P2W
Pattern 3 3P3W2M 1P2W 1P2W
Pattern 4 1P3W 1P3W
Pattern 5 3P3W2M 1P3W
Pattern 6 3P3W2M 3P3W2M
Pattern 7 3P3W3M 1P2W
Pattern 8 3P4W 1P2W