EasyManuals Logo

Hitachi RPI-4.0FSN4E Service Manual

Hitachi RPI-4.0FSN4E
429 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #217 background imageLoading...
Page #217 background image
5 Control system
205
5
SMGB0077 rev.0 - 01/2013
5.3.4 Automatic cooling/heating operation control
5.3.5 Preventive high-pressure increase control
This function is used to avoid an abnormal condition (alarm: 02) when the outdoor air ow drops due to seasonal winds
blowing against the air outlet. When CMC is enabled in cooling operation, PSC is enabled and Tc is greater than Tc1+4 °C,
operations with forced thermostat disabling are started.
Tc: Outdoor pipe temperature.
Tc1: Outdoor pipe temperature when the PSC is enabled.
PSC enabled: 3.60 MPa.
However, if this occurs more than 6 times during operations, thermostat stoppage is not forced. The cause of the stoppage
will be 13.

Table of Contents

Other manuals for Hitachi RPI-4.0FSN4E

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hitachi RPI-4.0FSN4E and is the answer not in the manual?

Hitachi RPI-4.0FSN4E Specifications

General IconGeneral
BrandHitachi
ModelRPI-4.0FSN4E
CategoryAir Conditioner
LanguageEnglish

Related product manuals