ACUIX High Speed Dome User Manual
Document 800-01023 Rev A 25
02/08
VCL - RS485
For VCL - RS485 protocol, the commonly used setting is 9600 baud, no parity.
SW5 - 11000001 (positions 1–8).
In above SW5–8 is ON to force reading from DIP switches. See DIP Switch Address
Override, page 26, for more information on setting SW5–8.
SW6 - 00100000 (positions 1–8) sets the ACUIX to 9600 baud with no parity.
IntelliBus™
SW5 - 00000001 (positions 1–8).
In above SW5–8 is ON to force reading from DIP switches. See DIP Switch Address
Override, page 26, for more information on setting SW5–8.
SW6 - 01100000 (positions 1–8) sets the ACUIX to 38400 baud with no parity.
Camera Address Settings
Address selection is via rotary switches SW1, SW2, SW3, and SW4.
Caution The ACUIX can be addressed from 0000 to 9999. The addressing
scheme may be restricted due to the limitations of the controller
being used to control the ACUIX. For example, the
HEGS5000/HEGS5001 controllers can control camera addresses 1
to 256. The HJZTP can control camera addresses 1 to 128.
Table 2-4 ACUIX Camera Addresses
Address Value
SW1 Units digit
SW2 Tens digit
SW3 Hundreds digit
SW4 Thousands digit