109 IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
Section 9: Programming
This section of the manual describes how to manually program the control panel from the built-in annunciator. Each subsection discusses
these menu options in detail. All options described in this section can be performed using the HFSS Honeywell Fire Software Suite.
9.1 UL 864 / UL 2572 Programming Requirements
9.2 Modules
This section lists the options available under the module option in the program menu. The following modules are available for the con-
trol panel: RA-100, RA-1000, & RA-2000 LCD annunciators, 5815XL SLC loop expander for SD devices, 6815 SLC Loop Expander
for IDP or SK devices, 5824 serial/parallel printer interface module, 5496 NAC Expander, RPS-1000 intelligent power module, 5880
LED I/O module, 5865 LED annunciator, ECS-50W, ECS-125W, ECS-INT50W or ECS-DUAL50W watt audio amplifier, ECS-VCM
voice control module, ECS-NVCM network voice control module, ECS-RVM remote voice module, and SK-NIC network interface
card.
9.2.1 Edit Modules
The features that can be edited when this option is selected are, module name, and class of wiring (Class A or Class B).
To edit an existing module, follow these steps:
1. Enter the installer code.
2. Select 7 for Program Menu.
3. Press 1 to enter module menu.
4. Press 1 to edit a module.
5. Use the up or down arrow to select the module you wish to edit. Then press ENTER.
IMPORTANT!
Before any customized programming is done, JumpStart should be run first. After JumpStart is run, thoroughly test the
system. The reason the system should be tested after JumpStart is because JumpStart automatically programs the system,
searching for and configuring all SLC and SBUS devices it finds. JumpStart allows you to confirm the integrity of the
installation prior to performing any custom programming. After determining that the hardware is properly installed, custom
programming can be performed.
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES:
This product incorporates field programmable software. In order for the product to comply with the requirements in the
Standard for Control Units and Accessories for Fire Alarm Systems, UL 864 and UL 2572, certain programming features or
options must be limited to specific values or not used at all as indicated below.
Programming
Option
Menu Item
Permitted
in
UL 864
(Y/N)
Permitted
in
UL 2572
(Y/N)
Possible Settings
Settings
Permitted in
UL 864
Settings
Permitted in
UL 2572
Time Options Auto-resound Yes Yes 4 hrs, 24hrs 4 hours if using
SWIFT devices
4 hours if using
SWIFT devices
Time Options Low AC Report
Delay
Yes Yes 0–30 hours 1–3 1–3
Display Oldest Event Y (Enabled) Yes Yes Yes & No Yes Yes
N (Disabled) No No Yes & No No No
Initial Delay 0-28 Yes Yes 0-28 3 3
Inter Message Delay 4-32 No No 4-32 4-32 4-28
Alarm Verification Alarm
Verification
Yes Yes 60-250
(Confirmation
period)
60 60
Auto Reset
ECS MIC Triggered
Event
Auto Reset
ECS MIC
Triggered
Event
Yes Yes Never
Timer Event
Disabled
Never
Timer Event
Disabled
Never
Timer Event
Disabled
ECS Input ECS Input Yes Yes Latching
Non-Latching
Latching Latching
Event Priority CO Alarm No No Yes & No No No
NOTE: If you are working on a networked system you will need to select which panel you want to program