191 IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
A.1.1 Two Wire Detectors
Table A.2 lists two-wire smoke detectors that are compatible with the fire control panel. The table is organized by manufacturer. The col-
umns show the number of detectors per loop that can be used.
.
IFP-300/ECS
Identifier
24H
Operating voltage Range
17.1 - 27.3 VDC
NOTE: The maximum number of smoke detectors per zone is determined by both the current draw and the impedance of the smoke detector.
If too many smoke detectors are used on any zone, false alarms could occur.
NOTE: Do not mix different models of detectors on any zone; false alarms could occur.
NOTE: Control unit Smoke Reset Time must be programmed for a number greater than or equal to the maximum reset time of the smoke
detector
Manufacturer
Model Name or Number (Base model
name or number in parenthesis.)
Compatibility ID
# per Loop
Head Base
Apollo
55000-350 (45681-200) 55000-350 45681-200 15 / loop
55000-250 (45681-200) 55000-250 45681-200 24 / loop
55000-225 55000-225 45681-255, 256
45681-200, 220, 232,
251, 252
15 / loop for Ion
Detectors
15 / loop for
Photo Electric
Detectors
55000-226 55000-226
55000-227 55000-227
55000-325 55000-325
55000-326 55000-326
55000-327 55000-327
55000-328 55000-328
Hochiki
SLR-24 HD-3
HSC-220R(HB-72)
NS6-220 OR NS4-220
(HB-3)
15 / loop
SLR-24H
SLR-24V
SLR-835 HD-3 14 / loop
SLR-835H HD-5
System Sensor
1400 A N/A 16 / loop
1451 (B401B) A N/A 16 / loop
2100 A N/A 20 / loop
2100T A N/A 20 / loop
2151 (B401) A N/A 16 / loop
2151T (B401) A N/A 16 / loop
2400 A N/A 16 / loop
2400TH A N/A 16 / loop
2451 (B401B) A N/A 16 / loop
2451TH (B401B) A N/A 16 / loop
2W-B A N/A 20 / loop
2WT-B A N/A 20 / loop
2WTA-B A N/A 1 / loop
2WTR-B A N/A 1 / loop
Table A.2 : Compatible Two-Wire Smoke Detectors Style B