IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017 58
4.18.2 Transmitter Activated by Dry Contacts
This section describes the connection of a UL 864 listed remote station transmitter to the IFP-300 FACP dry contacts. The FACP con-
tacts must be supervised by the remote station transmitter module using end-of-line resistors (ELRs) with a value determined by the
transmitter manufacturer. Power is also provided by the remote station transmitter manufacturer. Refer to the remote station transmitter
manufacturers manual for details.
Figure 4.51 Remote Station Transmitter