35 IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
4.6 RA-1000 Remote Annunciator Installation
The optional Model RA-1000 is a remote annunciator that utilizes a fireman’s key or access code to reset or silence. Up to 16 annuncia-
tors in any combination can be added to the IFP-300/ECS system.
Figure 4.16 Model RA-1000 Remote Annunciator, Front View
RA-1000 installation involves the following steps:
1. Make sure power is off at the panel.
2. Mount the RA-1000 in the desired location (see Section Figure 4.6.1).
3. Connect the RA-1000 to the panel (see Section Figure 4.6.2).
4. Use the DIP switches on the back of the RA-1000 to assign an ID# to the RA-1000 (see Section Figure 4.13.1).
5. The new RA-1000 module must be added to the system through programming. JumpStart
®
will add the module automatically (see
Section 8.1). You can also add it manually (see Section 9.2.2). Select a name, if desired (See “Editing Module ID” on page 110.).
4.6.1 Mounting the RA-1000
This section of the manual describes mounting the remote annunciator. The annunciator can be flush- or surface-mounted. Figure 4.17
shows the parts of the annunciator. Instructions for disassembling and mounting appear on the following pages
Figure 4.17 Annunciator Parts