IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017 20
1. The FACP can only support 5 devices w/LED’s on. This current draw has been added to the panels alarm current.
2. The SK-DUCT housing contains a vacant mount for a SK-RELAY (sold separately). Current draw for the SK-RELAY is calculated
by increasing the SK-RELAY row of the calculation sheet by one for each SK-RELAY used with a SK-DUCT.
3. SK-BEAM-T draws a maximum of 500mA from Auxiliary power only when the test feature is used. this should be considered when
determining auxiliary power capacity but not calculated into current requirements for day to day operation.
4. If using door holders, you do not need to consider door holder current for alarm/battery standby, because power is removed during
that time. However, during normal operation, door holders draw current and must be included in the 6.0A total current that can be
drawn from the panel.
5. Use next size battery with capacity greater than required.
6. Total does not include isolator devices or accessory bases.
3.7.4 Current Draw Worksheet SD for SLC Devices
Use Table 3.4 to determine current requirements during alarm/battery standby operation when SD SLC devices are installed. The IFP-
300 FACP supports up to a total of 127 SD SLC devices per loop, consisting of any combination of devices.
1
.
Multiply by the Derating Factor
x 1.25
Total ampere hours required
Device
Number of
Devices
Current per Device
Standby
Current
Alarm
Current
Table 3.3 Current Draw Worksheet for SK SLC Devices
Device
Number of
Devices
Current per Device
Standby
Current
Alarm
Current
For each device use this formula: This column X This column = Current per number of devices.
Fire Panel (Current draw from battery) 1 Standby: 190 mA
190 mA
Alarm: 250 mA
250 mA
Addressable SLC Devices
SD500-AIM Standby/Alarm: .55 mA
5
mA mA
SD500-MIM
mA mA
SD500-ARM
mA mA
SD500-PS
SD505-HEAT
mA mA
SD505-PHOTO
mA mA
SD500-ANM Aux. Pwr Standby: 8 mA
mA
Alarm: 60 mA
mA
SLC Standby/Alarm: .55 mA
mA mA
SD500-SDM SLC Standby/Alarm: .55 mA
mA mA
Aux. Pwr Standby: 20 mA
mA
Alarm: 106 mA
mA
SLC Accessory Bases
SD505-6RB Standby/Alarm: .082 mA
mA mA
SD505-6SB Aux. Pwr Standby: 1 mA
mA
Alarm: 32 mA
mA
SLC Standby/Alarm .082 mA
mA mA
SD505-DUCTR Aux. Pwr Standby: 20 mA
2
mA
Alarm: 62 mA
2
mA
SLC Standby/Alarm: .5 mA
mA mA
SD505-DTS-K None, included with SD505-DUCTR worst case.
SD505-DUCT SLC Standby/Alarm: .5 mA
mA mA
SLC Isolator Devices
SD500-LIM (254 max.) Standby/Alarm: .092 mA
mA mA
SD505-6IB (127 max.)
Table 3.4 Current Draw worksheet for SD Devices