19 IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
ECS-INT50W Internal Amplifier (8 max.) Standby: 52 mA
mA
Alarm @ 25V: 275 mA
mA
Alarm @ 70V: 310 mA
mA
ECS-NVCM Network Voice Control
Module
(1 max.) Standby/Alarm: 59 mA
mA mA
ECS-VCM Voice Control Module Standby: 70 mA
mA
Alarm: 100 mA
mA
ECS-SW24 Switch Expander (8 max.) Standby: 10 mA
mA
Alarm: 25 mA
mA
ECS-RPU Remote Paging Unit (7 max.) Standby: 70 mA
mA
Alarm: 100 mA
mA
ECS-LOC Local Operating Console
(includes RA-2000, RVM & SW-24)
(7 max.) Standby: 100 mA
mA
Alarm: 150 mA
mA
Network Cards
SK-NIC Network Interface Card (1 Max.) Standby/Alarm: 21 mA
mA mA
SK-FML Fiber Optic Multi Mode (1 Max.) Standby/Alarm: 53 mA
mA mA
SK-FSL Fiber Optic Single Mode (1 Max.) Standby/Alarm: 79 mA
mA mA
A
Total System Current
Wireless Modules
WSK-WGI Wireless Gateway Max current using ext supply 40 mA
mA mA
Max current SLC Power 24 mA
mA mA
Total System Current
Auxiliary Devices
4
Refer to devices manual for current rating.
IPDACT-2 IP Communicator (1 max.) Standby: 93 mA
mA
Alarm: 136 mA
mA
IPDACT-2UD IP Communicator (1 max.) Standby: 98 mA
mA
Alarm: 155 mA
mA
CELL-MOD/CELL-CAB-SK Standby: 55 mA
mA
Alarm: 100 mA
mA
Alarm/Standby: mA
mA mA
Alarm/Standby: mA
mA mA
Alarm/Standby: mA
mA mA
Alarm/Standby: mA
mA mA
B
Auxiliary Devices Current
Notification Appliance Circuits Refer to devices manual for current rating.
5495/5499 Power Supply 24 VDC One input circuit: 15 mA
mA
Both input circuit 30 mA
mA
Alarm: mA
mA
Alarm: mA
mA
Alarm: mA
mA
Alarm: mA
mA
C
Notification Appliances Current
mA
D
Total current ratings of all devices in system (line A + line B + C)
mA mA
E
Total current ratings converted to amperes (line D x .001):
AA
F
Number of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5):
H
G
Multiply lines E and F. Total standby AH
AH
H
Alarm sounding period in hours. (For example, 5 minutes = .0833 hours)
H
I
Multiply lines E and H. Total alarm AH
AH
J
Add lines G and I.
5
AH
Device
Number of
Devices
Current per Device
Standby
Current
Alarm
Current
Table 3.3 Current Draw Worksheet for SK SLC Devices