171 IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
12.2 SIA - IntelliKnight / Panels PI Modifier Reporting:
Events are sent to the central station as a variable length string:
The event format is:
EEZZZZ
Where:
EE Event code (2 characters)
ZZZZ Event parameter (up to four digits – not zero filled)
1. The account number is sent using an account block that is separate from the event block
2. Multiple events can be sent within a single event block. Events are separated by a “/” character.
3. Event parameter can be either a zone, point or module number.
4. When reporting by point is enabled, the communicator uses a “pi” event to supersedes the actual point event to report the module
the point is linked to.
5. Panel ID is not sent in the SIA event parameters.
For Example see Table 12.4:
System-based Wireless Gateway
Trouble
pi Exp. ID UT Point # UTNNXXPPPP 1 373 Exp. ID Point #
System-based Wireless Gateway
Trouble - restore
pi Exp. ID UJ Point # UJNNXXPPPP 3 373 Exp. ID Point #
Wireless Gateway Trouble pi Exp. ID UT Point # UTNNXXPPPP 1 373 Exp. ID Point #
Wireless Gateway Trouble re-
store
pi Exp. ID UJ Point # UJNNXXPPPP 3 373 Exp. ID Point #
SIA Reporting Format
Contact ID Reporting Format
SIA pi Modifier SIA
Event Description Module
ID # (If
Any)
SIA
Event
Codes
Parameter Fixed Length
Format NN -
panel ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
Qualifier Event
Code
Group # Contact #
Table 12.3 : Report Formats Table
Event
Report
Zone/ Point
Panel ID
Module
Zone ZZZZ
Point
ZZZZ
Fields Sent
SIA Event
Data
Fire Alarm-Zone Zone n/a n/a97 15 n/a EE-ZZ FA15
Fire Alarm-Zone Zone n/a n/a 05 n/a EE-Z FA5
Fire Alarm-Point Point n/a 01 n/a 123 EE-ZZ /EE-
ZZZ
pi01/FA123
Fire Alarm-Point Point n/a 33 n/a 203 EE-ZZ /EE-
ZZZ
pi11/FA203
Expander Trouble n/a n/a 11 n/a n/a EE-ZZ ET11
Auto Test n/a n/a n/a n/a n/a EE-Z RP0
Battery Trouble-Panel 32 n/a n/a 98 n/a n/a EE-ZZ YT98
Battery Trouble-Expander
18
n/a n/a 18 n/a n/a EE-ZZ YT18
SLC Loop Shorted n/a n/a 44 n/a n/a EE-ZZ ET44
Program Begin Panel
ID=32
n/a n/a n/a n/a n/a EE-Z LB0
Program Begin Panel ID=
22
n/a n/a n/a n/a n/a EE-Z LB0
AC Power Loss - Panel 22 n/a n/a 98 n/a n/a EE-Z AT0
Table 12.4 SIA- Panels - PI Modifier Reporting Examples