EasyManua.ls Logo

Honeywell Farenhyt Series - 4.18.2 Transmitter Activated by Dry Contacts

Honeywell Farenhyt Series
212 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
51 IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
2. Configure the circuit through programming (see Section 9.6).
Figure 4.43 Class B Notification Appliance Circuit Wiring
Maximum voltage drop is 3V per Class A circuit. See Table 4.4.
Class A Notification Wiring
You must use an appliance from the list of compatible appliances in Appendix A.
To install a Class A notification appliance circuit:
1. Wire the Class A notification appliances as shown in Figure 4.44.
Current Maximum Impedance
1.0A 3
1.5A 2
2.0A 1.5
2.5A 1.2
3.0A 1.0
Table 4.4 Maximum Impedance Class A
Alarm Polarity Shown
4.7 kEOL
Supervised
Power Limited
Notification Wiring
Max. Impedance: 1.5
All Circuits are Synchronized (Regulated). Rated at
27.4 VDC @ 3A Max.
!
CAUTION:
For proper system supervision do not use looped wire under terminals marked + and – of the Flexput connectors. Break wire runs to provide
supervision of connections.

Table of Contents

Other manuals for Honeywell Farenhyt Series

Related product manuals