7 IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017
Model/Module Description CS Local Auxiliary
Remote
Station
EVAC
5
Mass Notification (In-
Building)
5
068200 Motherboard Y Y Y Y Y Y
068600 control unit
operator
interface
YYYY Y Y
00VIP-50CB Amplifier
Enclosure
OOOO Y O
00VIP-125CB Amplifier
Enclosure
OOOO Y O
122774 Control unit
enclosure
YYYY Y Y
VIP/ECS-50W
50W Amp
1
OOOO Y YO
VIP/ECS-50WHV
50W Amp
1
OOOO Y Y
ECS-125W
125W amp
1
OOOO Y Y
ECS-125HV/VIP-
125HV
125W Amp
1
OOOO Y Y
ECS-INT50W
Internal 50W
1
Amp
OOOO Y Y
ECS-VCM Voice Control
Module
2
OOOO Y O
VIP-SW16 Switch
annunciator
OOOO O O
ECS-SW24 Switch
annunciator
OOOO O Y
ECS-CE4 Speaker
expander mod
3
OOOO O O
VIP-RM / ECS-RVM Remote
Microphone
Mod
4
OOOO O O
5815XL SLC Expander O O O O O O
6815 SLC Expander O O O O O O
ECS-NVCM Network Voice
Card
OOOO O O
SK-NIC Network Card O O O O O O
SK-FML / -FSL Fiber Module O O O O O O
Y = YES, N = NO, O = OPTIONAL
1. A maximum of eight 50/125 Watts Amplifiers for a maximum of 1000 Watts per ECS System.
2. A maximum of one Voice Control Module per ECS System.
3. A maximum of one Speaker Expander Module per Model VIP-50/125 or ECS-50W/ECS-125W.
4. A maximum of two Remote Microphone modules per ECS System.
5. When configured for Emergency relocation and evacuation equipment the system must meet Local configuration (Model IFP-
300) with a minimum of one amplifier (Model VIP-50/125 or ECS-50W/ECS-125W, or ECS-INT50W) and one Voice Control
Module (Model VIP VCM / ECS-VCM).
Table 2.2 NFPA Requirements for IFP-300ECS