IFP-300 / IFP-300ECS Manual P/N LS10145-001SK-E:B 12/18/2017 162
F4 Mapping Inhibited FT 2004 FTNN002004 1 570 00 004
F4 Mapping Inhibited Restoral FJ 2004 FJNN002004 3 570 00 004
Fire Reset OR 0 ORNN000000 1 401 00 000
Fire System Overridden FS 0 FSNN000000 1 245 00 000
Fire System Override Restore FR 0 FRNN000000 3 245 00 000
Ground fault condition trouble YP Exp. ID YPNNXX0000 1 310 Exp. ID 000
Ground fault condition trouble
restore
YQ Exp. ID YQNNXX0000 3 310 Exp. ID 000
Initial power up RR 0 RRNN000000 1 305 00 000
Local programming aborted or
ended with errors
LU 0 LUNN000000 1 628 00 000
Local programming begin LB 0 LBNN000000 1 627 00 000
Local programming ended
normally
LS 0 LSNN000000 1 628 00 000
Network node trouble (panel
missing)
EM Panel ID EMNNNN0000 1 334 Panel ID 000
Network node trouble restore
(panel no longer missing)
EN Panel ID ENNNNN0000 3 334 Panel ID 000
OPG Inhibit Trouble FT Group # +
1000
FTNN001GGG 1 320 00 Group #
OPG Inhibit Trouble Restore FJ Group # +
1000
FJNN001GGG 3 320 00 Group #
OPG Inhibit of Releasing Group SS Group # +
1000
SSNN001GGG 1 203 00 Group #
OPG Inhibit of Releasing Group
Restore
SR Group # +
1000
SRNN001GGG 3 203 00 Group #
Phone line 1 trouble detected LT 1 LTNN000001 1 351 00 000
Phone line 1 trouble restore LR 1 LRNN000001 3 351 00 000
Phone line 2 trouble detected LT 2 LTNN000002 1 352 00 000
Phone line 2 trouble restore LR 2 LRNN000002 3 352 00 000
Printer is off-line trouble VZ Exp. ID VZNNXX0000 1 336 Exp. ID 000
Printer is off-line trouble restore VY Exp. ID VYNNXX0000 3 336 Exp. ID 000
Printer is out of paper trouble VO Exp. ID VONNXX0000 1 335 Exp. ID 000
Printer is out of paper trouble re-
store
VI Exp. ID VINNXX0000 3 335 Exp. ID 000
Releasing Notif/Control Circuit
Disabled
pi Exp. ID SS Point # SSNNXXPPPP 1 203 Exp. ID Point #
Releasing Notif/Control Circuit
enabled
pi Exp. ID SR Point # SRNNXXPPPP 3 203 Exp. ID Point #
Remote programming aborted or
ended with errors
RU 0 RUNN000000 1 413 00 000
Remote programming ended nor-
mally
RS 0 RSNN000000 1 412 00 000
Repeater ground fault trouble EM 0103 EMNN000103 1 334 Panel ID 103
Repeater ground fault trouble re-
store
EN 0103 ENNN000103 3 334 Panel ID 103
Repeater missing trouble EM 0100 EMNN000100 1 334 Panel ID 100
SIA Reporting Format
Contact ID Reporting Format
SIA pi Modifier SIA
Event Description Module
ID # (If
Any)
SIA
Event
Codes
Parameter Fixed Length
Format NN -
panel ID
XX- SBUS ID
ZZZ- Zone #
PPPP- Point #
GGG- Group #
E- Emergency #
RRRR-Receiver #
Qualifier Event
Code
Group # Contact #
Table 12.3 : Report Formats Table