Galaxy 2 Series Installation Manual
05 Tamper (Latch)
The Tamper output is activated whenever a circuit tamper or lid tamper occurs. The output is not subject to
rearm: it latches on and remains active until a valid code, with the appropriate System Reset level, is entered.
06—24 Hour
The 24 Hour output is activated whenever a 24 Hour zone is activated. The output is not subject to rearm: it
latches on and remains active until a valid code, with the appropriate System Reset level, is entered.
08 0V Detector Reset (Pulse)
This output is always on (0V) but pulses for five seconds upon setting or system reset to reset any latching
detectors.
09 Set (Reflex)
The Set output is activated when the assigned groups on the system are set. This output is a Reflex output
and follows the set and unset status of the groups.
11 Comms Test (Pulse)
This output activates any time a test signal is sent to the Alarm Receiving Centre.
14 AC Fail (Reflex)
The AC Fail output indicates the status of the a.c. (mains) power supply. The output activates when the a.c.
supply fails or an AC Fail zone is activated. The output is reset when the a.c. supply is restored or the AC
Fail zone is closed. This output is subject to Parameter 56.7.4=Comms.Parameters.Power Delay.
15 Low Batt (Reflex)
The Low Batt output activates whenever the control unit stand-by battery falls below 10.5V or a Low Batt
zone is activated. The output is restored when the voltage rises above 10.5V or the Low Batt zone is closed.
16 Fire (Latch)
The Fire output is activated whenever a Fire zone is activated. It latches on and remains active until a valid
code (level 2 or above) is entered.
20 Confirm (Latch)
The Confirm output is activated when there have been activations on two separate zones: the second activa-
tion must occur within the Confirm Time Window. The zones do not have to be in the same group. Confirm
outputs will switch off when all groups which have been in alarm are unset.
NOTE: The Confirm output is used to give positive identification that a genuine intruder alarm condition has
occurred and to minimise the possibility of false alarm activations.
32 Omit (Reflex)
The Omit output is activated as soon as a zone is omitted from the system. The activation can be initiated
manually by omitting a zone at 11 = OMIT ZONES or by force omit at rearm. Response to either is control-
led by Option 56.7.06 = Comms.Parameters.Omit Sig.
53 - Outputs (cont’d)

Table of Contents

Other manuals for Honeywell Galaxy 2 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Galaxy 2 Series and is the answer not in the manual?

Honeywell Galaxy 2 Series Specifications

General IconGeneral
BrandHoneywell
ModelGalaxy 2 Series
CategorySecurity System
LanguageEnglish

Related product manuals