Figure 5-1 Settings Wizard
NO TE
Set the time and date correctly. Incorrect time and date will cause false fault analysis
during maintenance or repair, aecting the normal operation.
After you set network parameters, connect the UPS to the network over a network
cable, which allows you to remotely manage the UPS. If you do not need remote
management, retain the default network parameter settings.
Step 2 After you set parameters on the Settings Wizard screen, the system displays the
Bypass mode and No battery alarms, which do not need to be handled. Other
alarms need to be handled.
NO TE
After you set parameters on the Settings Wizard screen, choose System Info > Settings
> System Settings. Check that Requisite modules and Redundant modules match the
actual values.
If dry contact signals are connected to the system, choose System Info. > Settings >
Dry Contact Set. Check that the connected dry contacts have been enabled and that
the disconnected dry contacts have been disabled.
FusionModule2000-S Smart Modular Data Center
User Manual 5 Power-On Commissioning
Issue 07 (2022-09-30) Copyright © Huawei Technologies Co., Ltd. 136

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule2000-S and is the answer not in the manual?

Huawei FusionModule2000-S Specifications

General IconGeneral
BrandHuawei
ModelFusionModule2000-S
CategoryStorage
LanguageEnglish

Related product manuals