Tab Parameter Description
Humidity setpoint After the temperature and humidity
control type and the humidity value
under this type are set, the device
performs regulation based on the
settings.
40%–60% is recommended.
Comm
Settings
Modbus Comm
address
Enter the communication address
planned for the smart cooling product.
The management system
communicates with the smart cooling
product through this address. The
communication addresses of the two
smart cooling products connected to
the same management system must
be
dierent.
Step 6 After power-on, the compressor starts preheating, and the system generates a
compressor preheating alarm. The preheating takes 12 hours. The smart cooling
product cannot be started before the compressor preheating is complete. Choose
Running > Device Details > Compressor to view the remaining preheating time
of the compressor.
Figure 5-11 Remaining compressor preheating time
----End
5.2.2 Setting Parameters
5.2.2.1 Setting T/H Sensor Parameters
Path: Settings > System Settings > T/H Sensor
FusionModule2000-S Smart Modular Data Center
User Manual 5 Power-On Commissioning
Issue 07 (2022-09-30) Copyright © Huawei Technologies Co., Ltd. 163