Figure 5-12 T/H Sensor
Paramete
r
Description Recommended Value
Temperat
ure and
humidity
control
type
When the application scenario is
non-aisle containment, you are
advised to choose Return air.
Choose Cold aisle if cold aisle T/H
sensors are installed. Hot aisle is
not recommended.
Cold aisle
Temperat
ure
control
mode
The temperature inside the
equipment room or aisle is
controlled based on the average
value, maximum value, or
minimum value collected by
multiple sensors.
Average value
Humidity
alarm
mode
Set this parameter as required. -
Temperat
ure
setpoint
After the temperature and
humidity control type and the
temperature value under this type
are set, the device performs
regulation based on the settings.
● Return air: 18–45°C
recommended
● Supply air: 15–35°C
recommended
● Cold aisle: 15–35°C
recommended
● Hot aisle: 18–45°C
recommended
Cold aisle: 23°C recommended
Humidity
setpoint
After the temperature and
humidity control type and the
humidity value under this type are
set, the device performs regulation
based on the settings.
40%–60% is recommended.
50%
FusionModule2000-S Smart Modular Data Center
User Manual 5 Power-On Commissioning
Issue 07 (2022-09-30) Copyright © Huawei Technologies Co., Ltd. 164