EasyManua.ls Logo

Huawei FusionModule2000-S

Huawei FusionModule2000-S
346 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Step 16 Set the camera type.
1. Choose System Management > Devices > Device Management > Micro
Edge.
2. Select an IVS1800.
3. Right-click the camera for which you want to set the intelligent attribute and
choose
Congure from the shortcut menu.
4. Choose Video Channel > Video.
5. Set the checkpoint camera type.
----End
5.3.13 Linkage Control
5.3.13.1 High-Density Linkage
Prerequisites
You have obtained the IP address of the ECC800-Pro as well as the user name
and password used for WebUI login.
A PC with an IP address in the same network segment as that of the ECC800-
Pro is prepared, and the PC has connected to port WAN1 on the ECC800-Pro.
Enable linkage control function is set to Yes.
Commissioning Procedure
Step 1 Go to the linkage control page and check that Enable linkage control function is
set to Yes. Set the linkage control signals in the high-density scenario to on.
Figure 5-76 Setting linkage control in the high-density scenario
----End
5.3.13.2 Fire Control Linkage
Context
The passive dry contact alarm signal of the customer's
re extinguishing
system can be linked to an AI/DI port of the ECC800-Pro to shut down the
smart cooling product, preventing the
re from escalating due to air supply.
NO TE
An active dry contact signal of the customer's re extinguishing system cannot be
connected to the ECC800-Pro AI/DI port.
FusionModule2000-S Smart Modular Data Center
User Manual 5 Power-On Commissioning
Issue 07 (2022-09-30) Copyright © Huawei Technologies Co., Ltd. 245

Table of Contents

Related product manuals