Tab Parameter Description
Floor water overow
alarm action
Set the action of the device if there is
water overow on the oor based on
the actual scenario.
Shutdown: The device shuts down
when a oor water overow alarm
is generated.
Inactivity: The device runs as usual
when a
oor water overow alarm
is generated.
Only indoor fan running: Only the
indoor fan runs when a
oor water
overow alarm is generated.
Humidier stopped: Only the
humidier is stopped when a oor
water overow alarm is generated.
In-cabinet water
overow alarm action
Set the action of the device if there is
water overow in the cabinet based on
the actual scenario.
Shutdown: The device shuts down
when an in-cabinet water overow
alarm is generated.
Inactivity: The device runs as usual
when an in-cabinet water overow
alarm is generated.
Only indoor fan running: Only the
indoor fan runs when an in-cabinet
water
overow alarm is generated.
Humidier stopped: Only the
humidier is stopped when an in-
cabinet water overow alarm is
generated.
T/H Sensor Temperature and
humidity control type
When the application scenario is non-
aisle containment, you are advised to
choose Return air. Choose Cold aisle
if cold aisle T/H sensors are installed.
Hot aisle is not recommended.
Temperature setpoint After the temperature and humidity
control type and the temperature
value under this type are set, the
device performs regulation based on
the settings.
Return air: 26–35°C recommended
Supply air: 18–24°C recommended
Cold aisle: 18–24°C recommended
Hot aisle: 26–35°C recommended
FusionModule2000-S Smart Modular Data Center
User Manual 5 Power-On Commissioning
Issue 07 (2022-09-30) Copyright © Huawei Technologies Co., Ltd. 162