Tab Parameter Description
Floor water overow
alarm action
Set the action of the device if there is
water overow on the oor based on
the actual scenario.
● Shutdown: The device shuts down
when a oor water overow alarm
is generated.
● Inactivity: The device runs as usual
when a
oor water overow alarm
is generated.
● Only indoor fan running: Only the
indoor fan runs when a
oor water
overow alarm is generated.
● Humidier stopped: Only the
humidier is stopped when a oor
water overow alarm is generated.
In-cabinet water
overow alarm action
Set the action of the device if there is
water overow in the cabinet based on
the actual scenario.
● Shutdown: The device shuts down
when an in-cabinet water overow
alarm is generated.
● Inactivity: The device runs as usual
when an in-cabinet water overow
alarm is generated.
● Only indoor fan running: Only the
indoor fan runs when an in-cabinet
water
overow alarm is generated.
● Humidier stopped: Only the
humidier is stopped when an in-
cabinet water overow alarm is
generated.
T/H Sensor Temperature and
humidity control type
When the application scenario is non-
aisle containment, you are advised to
choose Return air. Choose Cold aisle
if cold aisle T/H sensors are installed.
Hot aisle is not recommended.
Temperature setpoint After the temperature and humidity
control type and the temperature
value under this type are set, the
device performs regulation based on
the settings.
● Return air: 26–35°C recommended
● Supply air: 18–24°C recommended
● Cold aisle: 18–24°C recommended
● Hot aisle: 26–35°C recommended
FusionModule2000-S Smart Modular Data Center
User Manual 5 Power-On Commissioning
Issue 07 (2022-09-30) Copyright © Huawei Technologies Co., Ltd. 162