Tab Parameter Description
DO_2 ● If this parameter is set to Smoke &
Water only, DO_2 acts according to
DO_2 action when a smoke or
water overow alarm is generated.
● If this parameter is set to Critical
alarm, DO_2 acts according to
DO_2 action when a critical alarm
is generated.
● If this parameter is set to Major
alarm, DO_2 acts according to
DO_2 action when a major alarm is
generated.
● If this parameter is set to Alarm,
DO_2 acts according to DO_2
action when a critical alarm, major
alarm, or warning is generated.
● If this parameter is set to Startup
status, DO_2 acts according to
DO_2 action when the unit is
started.
● If this parameter is set to No, no
alarm is generated when DO_2 is
disconnected.
● If this parameter is set to Power
abnormal, DO_2 acts according to
DO_2 action when a power
exception alarm is generated.
DO_1 action
This parameter can be set to On or
O, and is used together with DO_1.
For details, see DO_1 description.
DO_2 action This parameter can be set to On or
O, and is used together with DO_2.
For details, see DO_2 description.
FusionModule2000-S Smart Modular Data Center
User Manual 5 Power-On Commissioning