Procedure
Step 1 Apply to the equipment room network administrator for a xed IP address.
Step 2 Set the IP address, subnet mask, and default gateway on the ECC800-Pro WebUI.
Table 5-51 IP parameters
Path Parameter Default
Value
Setting
System
Settings >
System
Parameter
s >
Monitor IP
> WAN_1
IP 192.168.8.1
0
Set this parameter based on the IP
address assigned by the network
administrator.
Subnet
mask
255.255.25
5.0
Set this parameter based on the
subnet mask assigned by the network
administrator.
Default
gateway
192.168.8.1 Set this parameter based on the
default gateway address assigned by
the network administrator.
Step 3 Set SNMP parameters.
1. Choose System Settings > NMS Application > SNMP.
2. Set SNMP Version to SNMPv3 and set SNMP port number to the required
port number or retain its default value 161.
3. Click Submit under SNMP.
4. Click Add under SNMPv3.
5. Set User name, set Authentication protocol to SHA or MD5, set Privacy
protocol to AES or DES, and specify MD5/SHA password,
Conrm MD5/SHA
password, DES/AES password, and Conrm DES/AES password.
NO TE
Set User name, MD5/SHA password, and DES/AES password to any character
strings that meet the system requirements. Note that MD5/SHA password and
DES/AES password must be set to dierent values. Record the settings.
MD5 and DES are insecure protocols. Therefore, you are advised to set
Authentication protocol to SHA or set Privacy protocol to AES.
6. Set Password validity period and Advance expiration notication (days).
7. After setting the parameters, click Conrm.
8. Click Add under SNMP Trap.
9. Set Trap target address and Trap port, set SNMP version to SNMPv3, and
specify SNMPv3 user name. Set Trap target address to the IP address of the
NMS server and set Trap port to the port dened by the user.
10. After setting the parameters, click
Conrm.
11. Click Export in the Mib File pane, export the MIB le, and send it to the
development engineers of the NMS.
----End
FusionModule2000-S Smart Modular Data Center
User Manual 5 Power-On Commissioning
Issue 07 (2022-09-30) Copyright © Huawei Technologies Co., Ltd. 260

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule2000-S and is the answer not in the manual?

Huawei FusionModule2000-S Specifications

General IconGeneral
BrandHuawei
ModelFusionModule2000-S
CategoryStorage
LanguageEnglish

Related product manuals