Figure 6-2 Troubleshooting owchart
After an alarm is cleared, prepare a report to record the alarm handling process.
NO TE
Common alarm references are as follows:
Data center infrastructure alarm reference in the online help of the management system
Alarm references in documents delivered with components
Alarm reference in this document
Alarm reference obtained from technical support
It is recommended that the alarm handling report consists of information about the alarm
occurrence time, location, symptom, fault locating process, alarm handling process, and
alarm prevention solutions.
FusionModule2000-S Smart Modular Data Center
User Manual 6 Operation and Maintenance