EasyManua.ls Logo

Huawei FusionModule2000-S

Huawei FusionModule2000-S
346 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 6-26 Removing a temperature sensor
Step 2 Install the spare temperature sensor, bind it to the original position using cable
ties, and connect cables to it.
NO TICE
When installing temperature sensors, bind the cables behind the sensors to the
cable bridge, keeping them 20 mm away from the sensor probes.
Temperature sensors must not be in touch with metal parts or cabinets.
Keep the temperature sensors facing the inside of the cabinets to ensure
accurate measurement of cabinet interior temperatures.
----End
Follow-up Procedure
Check whether the new temperature sensor works properly. If its status is
displayed on the WebUI of the ECC800-Pro, the new temperature sensor works
properly.
FusionModule2000-S Smart Modular Data Center
User Manual 6 Operation and Maintenance
Issue 07 (2022-09-30) Copyright © Huawei Technologies Co., Ltd. 320