Figure 6-27 Connecting a conversion cable to a water detector
Step 2 Replace a water detection cable.
1. Remove the faulty water detection cable from the port.
2. Connect a new water detection cable.
Figure 6-28 Connecting a new water detection cable
(1) Conversion cable end B, connected to the
water detection cable
(2) Water detection cable end A, connected to
the conversion cable
NO TE
The water detection cable and conversion cable are interconnected through male and
female connectors.
Step 3 Check whether the new water detector works properly. Connect the network cable
between the water detector and ECC, immerse the water detection cable in water,
and check whether an alarm is generated. If an alarm is generated, the
replacement is complete.
Step 4 Wipe dry the water detection cable. The alarm disappears automatically.
----End