EasyManuals Logo

Huawei FusionModule2000-S User Manual

Huawei FusionModule2000-S
346 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #34 background imageLoading...
Page #34 background image
Do not store combustible materials in the battery room. Keep such materials
at least 3 m away from the battery room.
A battery room deployed outdoors should be at least 3.0 m away from the
following places: restricted areas, combustible warehouses, dangerous goods,
high-stacking warehouses, power infrastructure, public roads, and buildings.
The battery room should be isolated from the adjacent area by
re
compartmentation. Holes should be sealed by restop material. The re
resistance and thermal insulation capabilities should be the same as that of
the partition wall.
The battery room should be equipped with re extinguishers lled with
halogenatedane,
heptauoropropane, peruorohexanone, carbon dioxide, or
dry powder. Each re protection unit should be equipped with at least two re
extinguishers, which should be checked and replaced periodically.
The battery room should be equipped with cabinet-level or room-level CO
sensors, smoke sensors, and temperature sensors. It is recommended that H
2
sensors and open
ame sensors be deployed. At least two sensors of each
type should be deployed, and the automatic
re alarm system should be
enabled.
The battery room should be equipped with independent air conditioners and
ventilation ducts, which must be isolated form those for other equipment
areas or
oce areas. If ventilation ducts are shared, re dampers must be
installed for the battery room. The ventilation and exhaust system must
interact with the
re alarm system and be able to handle ammable gases
with a concentration lower than 25% lower ammability limit (LFL).
The battery room should be equipped with a halogenatedane or
peruorohexanone gas re extinguishing system, which should interwork with
the
re alarm system. After the extinguishing agent is released, the battery
room should meet the requirement on ame extinguishing concentration
within 10 min.
The battery room should be equipped with re extinguishing facilities such as
a dry-type water spray or water mist pipe network to cope with the risk of
reignition or
re spreading after the battery re is extinguished.
The battery room should be equipped with pressure relief explosion-proof
devices or pressure relief channels (such as glass windows and magnetic lock
doors) with equivalent areas. According to the NFPA 68 or GB 50016
standard, if side pressure relief is adopted, a protective fence or wall should
be installed outside the pressure relief channels, and the fence or wall should
be at least 12 m away from the pressure relief wall.
The
re alarm system should interact with the ventilation and exhaust system
and automatic re extinguishing system, able to trigger the energy storage
system to disconnect the charging and discharging circuits.
Fire alarms in the battery room should be automatically reported to the re
supervision center. If the battery room is unattended, an automatic re alarm
system must be deployed to report re alarm signals to the remote
management center.
Recycling
Dispose of waste batteries in accordance with local laws and regulations. Do
not dispose of batteries as household waste. Improper disposal of batteries
may result in environmental pollution or an explosion.
FusionModule2000-S Smart Modular Data Center
User Manual 1 Safety Information
Issue 07 (2022-09-30) Copyright © Huawei Technologies Co., Ltd. 23

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei FusionModule2000-S and is the answer not in the manual?

Huawei FusionModule2000-S Specifications

General IconGeneral
BrandHuawei
ModelFusionModule2000-S
CategoryStorage
LanguageEnglish

Related product manuals