The power and thermal measurements that are shown in Table 23 on page 151 were obtained in the
specic operating environment and under the conditions described. These measurements are presented
as an illustration; measurements that are obtained in other operating environments might vary. Conduct
your own testing to determine specic measurements for your environment.
Table 23. Power consumption examples per enclosure
Model and type Conguration
Total power
consumption
Caloric value (BTU/hr)
Storwize V7000 2076-724 and
Storwize V7000 2076-U7B
1 enclosure with up to
24 dual port NVMe
drives (1.92 TB, 3.84
TB, 7.68 TB, 15.36 TB),
3 host adapters
711 W 2426
2076-92F
1 enclosure with 92 10
TB nearline SAS drives
848 W -
2076-92F
1 enclosure with 92 15
TB tier 1 flash drives
748 W -
Each Storwize V7000 enclosure contains two PSUs for redundancy. The total power consumption values
represent the total power that is drawn by both PSUs.
Environmental requirements
System airflow is from the front to the rear of each enclosure:
• Airflow passes between drive carriers and through each enclosure.
• Airflow for the upper 4U of the 5U enclosure enters the front, passes between the disk drives, and exits
through the large fans in the rear of the enclosure.
• Airflow for the lower 1U of the 5U enclosure is driven through the power supplies via 40 mm X 56 mm
fans. Air continues through the chassis cooling the ESMs or controllers and exits the rear of the
enclosure.
• The combined power and cooling module exhausts air from the rear of each canister.
Ensure that your environment falls within the ranges that are shown in Table 24 on page 151
.
Table 24. Temperature requirements
Environment
Ambient
temperature
Altitude Relative humidity
Maximum wet bulb
temperature
Operating
5°C to 35°C
(41°F to 95°F)
0 - 3048 m
(0 - 10000 ft)
8% to 80%
noncondensing
23°C (73°F)
Non-operating
1°C to 50°C
(34°F to 122°F)
-305 to 12192 m
(-1000 to 40000 ft)
8% to 80%
noncondensing
27°C (80°F)
Storage
1°C to 60°C
(34°F to 140°F)
5% to 80%
noncondensing
29°C (84°F)
Shipping
-40°C to 60°C
(-40°F to 140°F)
5% to 100%
condensing, but not
precipitating
Note: Decrease the maximum air temperature by 1 degree C per 300 m above 900 m.
Dimensions and weight requirements for rack installation
Appendix C. Control enclosure requirements
151