1-16 TS3400 Tape Library Maintenance Information
0220
A timeout error occurred
when ejecting cartridge
from Drive #1.
CHK 0220
1. Confirm the drive connection.
2. Confirm the media is compatible.
3. Cycle the power and try again.
4. Replace the drive canister (page 9-11).
5. Replace the Drive Docking Card (page 9-19).
6. Replace the Library Control Blade (page 9-8).
7. Replace the Back Board assembly (page 9-37).
8. Replace the TS3400 Tape Library chassis (page 9-44).
0221
The Loop ID setting for
Drive #1 failed.
CHK 0221
1. Confirm the drive connection.
2. Verify the drive port configuration (Web User Interface:
Configure Library Physical).
3. Cycle the power and try again.
4. Replace the drive canister (page 9-11).
5. Replace the Drive Docking Card (page 9-19).
6. Replace the Library Control Blade (page 9-8).
7. Replace the Back Board assembly (page 9-37).
8. Replace the TS3400 Tape Library chassis (page 9-44).
0222
Drive #1 is in Prevent
Medium Removal state,
disabling cartridge
removal.
CHK 0222
1. Release the Drive #1 Prevent Medium Removal state from
the host.
2. Cycle the power and try again.
3. Replace the drive canister (page 9-11).
4. Replace the Drive Docking Card (page 9-19).
5. Replace the Library Control Blade (page 9-8).
6. Replace the Back Board assembly (page 9-37).
7. Replace the TS3400 Tape Library chassis (page 9-44).
0300
Invalid data was sent to
Drive #2.
NAK was detected.
CHK 0300
1. Confirm the drive connection.
2. Cycle the power and try again.
3. Replace the Library Control Blade (page 9-8).
4. Replace the drive canister (page 9-11).
5. Replace the Drive Docking Card (page 9-19).
6. Replace the Back Board assembly (page 9-37).
7. Replace the TS3400 Tape Library chassis (page 9-44).
0301
A timeout error occurred
while waiting for response
from Drive #2.
CHK 0301
0303 Drive #2 is disconnected. CHK 0303
0305 Drive #2 is busy. CHK 0305
0306
Drive #2 failed to execute
a command because it is
not mounted.
CHK 0306
0320
A timeout error occurred
when ejecting cartridge
from Drive #2.
CHK 0320
1. Confirm the drive connection.
2. Confirm the media is compatible.
3. Cycle the power and try again.
4. Replace the drive canister (page 9-11).
5. Replace the Drive Docking Card (page 9-19).
6. Replace the Library Control Blade (page 9-8).
7. Replace the Back Board assembly (page 9-37).
8. Replace the TS3400 Tape Library chassis (page 9-44).
Table 1-2. Drive error codes (continued)
Code (H) Description
Panel
indication
Action Required