ULTRAFLOW®54(H)/(J)
KamstrupA/S∙TechnicalDescription∙5512‐1554_J1_GB_04.2018
75
q
p
[m³/h] [imp/l] [l/pulse] CC [ms] (E=1) [ms] (E=4) [ms] (E=5) [ms] (E=6)
150 1 33 3.9 - - - Default
150 10 34 - 20 - -
150 25 64 - 20 - -
150 100 35 - 20 50 100
150 250 65 - 20 50 100
150 1000 36 - 20 50 100
150 2500 66 - 20 50 100
250 0.6 43 3.9 - - - Default
250 10 34 - 20 - -
250 25 64 - 20 - -
250 100 35 - 20 50 100
250 250 65 - 20 50 100
250 1000 36 - 20 50 100
250 2500 66 - 20 50 100
400 0.4 63 3.9 - - - Default
400 100 35 - 20 50 -
400 250 65 - 20 50 100
400 1000 36 - 20 50 100
400 2500 66 - 20 50 100
600 0.25 14 3.9 - - - Default
600 100 35 - 20 50 -
600 250 65 - 20 50 -
600 1000 36 - 20 50 100
600 2500 66 - 20 50 100
1000 0.15 24 3.9 - - - Default
1000 (0.25) 4 14 3.9 - - - *)
1000 100 35 - 20 50 -
1000 250 65 - 20 50 -
1000 1000 36 - 20 50 100
1000 2500 66 - 20 50 100
*) Spare part for ULTRAFLOW
®
type 65-S/R/T. Configured 65-5-FGCR. No flow info.
Meter factor Pulse duration
Table 27. Programming options as to meter factor (CC) and
pulse duration (E) for ULTRAFLOW
®
54 DN150...300.
Based on a q
p
value a meter factor in Table 27 is chosen. The valid pulse durations are listed in the same line as
the chosen meter factor.
Example: For ULTRAFLOW
®
54, q
p
400 m
3
/h, meter factor, 100 l/pulse (CC=35) is required. Based on this meter
factor, pulse durations 20 (E=4) or 50 (E=5) milliseconds can be selected.
Default values in Table 27 are programming values for ULTRAFLOW
®
54 DN150...300 when connected to a Kamstrup
MULTICAL
®
calculator.