Safe torque o (S
TO)
This funcon corresponds to a "Stop 0" according to EN 60204.
The motor cannot generate torque and movements of the drive.
DANGER!
With the "Safe torque o" (S
TO) funcon, no "emergency switching o" in terms with
EN 60204‑1 can be executed without addional measures. There is no electrical isolaon
between the motor and inverter and no service switch or maintenance switch!
Possible consequence: Death or severe injuries
▶
"Emergency switching o" requires electrical isolaon, e. g. by a central mains contactor.
DANGER!
Automac r
estart if the request of the safety funcon is deacvated.
Possible consequences: Death or severe injuries
▶
You must provide external measures according to EN ISO 13849‑1 which ensure that the
drive only restarts aer a conrmaon.
DANGER!
The power supply is not safely disconnected.
Dea
th or serious injury due to electrical voltage.
▶
Turn o the power supply.
Precondions
Moon c
aused by external forces must be prevented by addional measures such as
mechanical braking.
The restart must be set. See chapter "Restart". ^ 111
Funconal descripon
How to safely disconnect the drive:
1.A safety sensor requests the safety funcon.
2.The transmission of the pulse width modulaon is safely switched o by the safety unit.
The power drivers do not generate a rotang eld anymore.
3.The inverter switches to the STO acve device status (status word 0x6041, Bit15 = 0).
The motor is safely switched to torqueless operaon (STO).
Funconal sa
fety
Safety funcons
Safe torque o (STO)
118