Detecng and eliminang EMC in
terferences
Trouble Cause Remedy
Interferences of analog setpoints of your own
or other de
vices and measuring systems
Unshielded motor cable has been used Use shielded motor cable
Shield contact is not extensive enough Carry out opmal shielding as specied
Shield of the motor cable is interrupted, e. g. by
terminal strips, switches etc.
•
Separ
ate components from other component
parts with a minimum distance of 100 mm
•
Use motor chokes or motor lters
Addional unshielded c
ables inside the motor
cable have been installed, e. g. for motor
temperature monitoring
Install and shield addional cables separately
Too long and unshielded cable ends of the
motor cable
Shorten unshielded cable ends to max. 40 mm
Conducted interference level is exceeded on the
supply side
Terminal strips for the motor cable are directly
located next to the supply terminals
Spaally separate the terminal strips for the
motor cable from mains terminals and other
control terminals with a minimum distance of
100 mm
Mounng plate varnished Opmize PE connecon:
•
Remove varnish
•
Use zinc-coated mounng plate
HF short circuit Check cable roung
Malfuncons of the eldbus communicaon or
exceedance of the permissible interference
levels
Shield contact is not extensive enough Before leaving the control cabinet, connect the
shield of the eldbus cable with the
equipotenal bonding system (e. g. mounng
plate) on a large surface.
Shield connecon on the inverter only
Shield of eldbus cable connected on one side
only
Shield connecon on both sides
Electrical ins
tallaon
EMC-compliant installaon
Detecng and eliminang EMC interferences