Preparaon
Further data and in
formaon for mechanical mounng:
4Control cabinet structure ^ 33
4Dimensions ^ 95
Installaon clearances
•
Maintain the specied installaon clearances above and below to the other installaons.
•
Several devices of the same series can be lined up directly, regardless of the device size. No
installaon clearance is required between the devices.
Mechanical installaon
•
The mounng locaon and material must ensure a durable mechanical connecon.
•
Do not mount onto DIN rails!
•
In case of connuous vibraons or shocks use vibraon dampers. If non-conducve
vibraon dampers are used, an EMC-compliant design must be ensured.
How to mount the inverters onto the mounng plate.
Precondions:
•
Mounng plate with conducve surface
Required:
•
Tool for drilling and thread cung
•
Screwdriver
•
Screw and washer assemblies or hexagon socket screws with washers.
1.Prepare mounng plate with corresponding threaded holes.
2.Fit screws and washers (if applicable).
3.Do not yet ghten the screws.
4.Mount the inverter on the prepared mounng plate via keyhole suspension.
5.Only ghten the screws hand-ght.
6.Pre-assemble further units if necessary.
7.Adjust the units.
8.Screw the units onto the mounng plate.
The inverter and any other units are mounted on the mounng plate. You can begin with the
wiring.
Screw and washer assemblies or hexagon socket screws with washers are recommended..
M5 x ≥ 10 mm for devices up to and including 2.2 kW
M5 x ≥ 12 mm for devices up to and including 11 kW
M6 x ≥ 16 mm for devices up to and including 22 kW
M8 x ≥ 16 mm for devices up to and including 110 kW
Mechanical ins
tallaon
Preparaon
46