Lenze i750 - Motor Connection

Lenze i750
184 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Motor c
onnecon
Only use motors suitable for the inverter operaon.
Insulaon resistance (EN 60034): max. û ≥ 1.5 kV, max. du/dt ≥ 5 kV/µs
Motor cable lengths
The r
ated data for the motor cable length must be observed.
Keep the motor cable as short as possible as this has a posive eect on the drive
behaviour and the EMC.
Switching in the motor cable
Switching on the motor side of the inverter is permissible:
F
or safety shutdown (emergency stop).
In case several motors are driven by one inverter (only in V/f operang mode).
Please note the following:
The switching elements on the motor side must be dimensioned for with the
maximum occurring load.
Electrical ins
tallaon
Motor connecon