Supply voltage c
onnecon
An external 24 V supply voltage to X5:24E/GE is necessary for supplying the control
electronics.
If the control electronics are supplied independently of the AC system of the supplier, the
inverter can also be congured when the AC grid is turned o. Communicaon via exisng
networks also remains available.
DANGER!
Loss of the safe isolaon
Sa
fe isolaon of the control card from the mains potenal is deacvated when the motor and
motor holding brake are connected via a system cable AND X5 and X107 are supplied by a
common power supply unit. This also applies when using a SELV/PELV power supply unit.
Possible consequences: Electric shock in the event of a fault.
▶
Supply X107 and X5 by separate SELV/PELV power supply units if the motor and motor
holding brake are connected via a system cable.
Connecon of mot
or temperature monitoring
Terminal X109 can be used with inverters < 22 kW either for temperature
monit
oring with PTC/TKO or for One Cable Technology (OCT).
4Connecon of one cable technology (OCT) via HIPERFACE DSL® ^ 69
If the terminal X109 is used, e. g. to connect an external PTC thermistor (PTC) or
a thermal c
ontact, ensure at least one basic insulaon to the potenals of
motor, mains and control terminals to not restrict the safe separaon of the
control terminals.
Use Connecon of P
TC or thermal contact
Connecon Terminal X109: T1
Terminal X109: T2
Sensor types PTC single sensor (DIN 44081)
PTC triple sensor (DIN 44082)
Thermal contact
Electrical ins
tallaon
Supply voltage connecon
62