Fieldbus cables, networks
Please observe the following r
ecommendaons for trouble-free operaon, especially in the
event of Ethernet-based networks.
•
Cables and wiring mus
t meet the specicaons and requirements of the network being
used to allow reliable operaon of the network in typical installaons. In this context, also
observe the recommendaons for acon of the respecve user organizaon.
•
Lay network cables separately from power cables. Maintain as large a distance as possible
to the motor cables which are subject to interference.
•
To avoid compensang currents via the shielding of the network cable, install an
independent, low-resistance equipotenal bonding over the shortest possible distance
parallel to the network cable. This applies in parcular to long cables.
•
Observe bending radii according to manufacturer informaon. Minimum bending radii of
10 x cable diameter or 20 x diameter for frequent manipulaon of the cables are
standard.
•
Fix longer cables 30 cm aer the connecon point.
•
Before leaving the control cabinet, connect the shield of the network cable with the
equipotenal bonding system (e. g. mounng plate) on a large surface.
Patch cable/CAT5 cables:
The appropriate patch cable for the EtherCAT c
onnecon of the axes is included
in the scope of supply.
RJ45 plug c
onnecons:
•
RJ45 plug connecons only funcon properly if they are not subjected to mechanical stress
or lateral forces.
•
For all communicaon modules of the i-series, the connecon of the cable shielding at the
RJ45 sockets is carried out as follows:
•
At the rst RJ45 socket, the shielding is directly connected to funconal earth (FE).
•
At the second RJ45 socket, the shielding is connected to funconal earth (FE) via an RC
element.
This measure prevents potenal equalizaon currents and the resulng interference
eects (see also IEC 61158-2, secon 11.8.7).
Note: High-frequency interference is dissipated via the low-impedance capacitor to
funconal earth (FE), but for low-frequency signals this system has a high loop impedance.
Measuring systems that use low impedance test signals therefore indicate too high
impedance values for the shielding at the second RJ45 socket
Electrical ins
tallaon
EMC-compliant installaon
Fieldbus cables, networks
53