IMPULSE•G+ Mini Advanced Instruction Manual – March 2014
5-63
Figure 5-25: Motor Protection Operation Time
Power Loss Ride Thru
Parameter
Code Name Function Range
Initial
Value
Access
Level
L02.01 Power-Loss Selection Enables/disables the Power Loss
Ride Thru function
00–02 00 Adv
00 Disable Disabled
01 Enable Drive will restart if power returns
within L02.02
02 CPU Power Active Drive will restart if power returns
before control supply shutdown
L02.02 Power-Loss Ride Thru Time Power Loss Ride Thru time 0.0–25.5 sec Varies Adv
L02.03 Power-Loss BaseBlock Time Output turn on delay after power
resumes
0.1–5.0 sec Varies Adv
L02.04 Power-Loss V/F Ramp Time Voltage recovery time after speed
search is complete
0.0–5.0 sec Varies Adv
L02.05 PUV Detection Level Under voltage fault detection
level
150–210 VDC
300–420 VDC
190/380 Adv
L02.07 Power-Loss Ride Thru Accel Acceleration time after a Power
Loss Ride Thru
0.0–25.5 0.0 Adv