IMPULSE•G+Mini Advanced Instruction Manual – March 2014
6-10
Fault Display and Corrective Actions at Auto-Tuning
The following are fault displays and corrective actions at auto-tuning. If any of the following faults
are found, the digital operator displays that fault’s contents; the motor coasts to stop if it is under
operation. Fault contact output or minor fault contact output does not operate.
Fault Display Fault or Indicator Name/Description Corrective Action
Er-01
Fault
Motor Data Fault. Motor data was entered
incorrectly for auto-tuning. Relationship between
motor HP and motor rated current fault. Input
motor rated current and motor no-load current
fault don’t match.
Check the T1 parameters.
Check inverter and motor capacity
Check motor rated current and no-load current.
Er-02
Minor Fault
Alarm. The minor fault is detected during auto-
tuning.
Check the T1 parameters.
•Check wirings
Disconnect motor from load.
Er-03
STOP Key
STOP Key Input. The stop key is pressed during
auto-tuning.
Er-04
Resistance
Line to Line Resistance Fault. Auto-tuning is not
completed within the expected time. The auto-
tuning is outside the parameter setting.
Check the T1 parameters.
Check motor wiring.
Disconnect motor from load.
Er-05
No-Load Current
No-load Current Fault. Auto-tuning is not
completed within the expected time. The auto-
tuning is outside the parameter setting.
Er-08
Rated Slip
Rated Slip Fault. Auto-tuning is not completed
within the expected time. The auto-tuning is
outside the parameter setting.
Er-09
Accelerate
Acceleration Fault (rotating auto-tuning only).
The motor did not accelerate at the expected time.
Increase B05.01 (acceleration time).
If C07.01 and C07.02 (torque limit value) are
decreased, increase values.
Disconnect motor from load.
Er-11
Motor Speed
Motor Speed Fault (rotating auto-tuning only).
The motor speed was over 100% at auto-tuning
(vector control without PG only).
Increase B05.01 (acceleration time).
Disconnect motor from load.
Er-12
I.det.Circuit
Current Detection Fault. Current exceeded the
motor rated current.
Release brake.
Check for open motor lead.
End 1
V/f Oversetting
Excess V/f setting * (rotating auto-tuning only).
The torque reference exceeded 20% and no load
current exceeded 80%.
Check the T1 parameters.
Disconnect the motor from the load.
End 2
Saturation
Motor Iron Core Saturation Coefficient Fault
(rotating auto-tuning only). Since the motor iron
core saturation coefficient could not be auto-tuned
within the set time, tentative value is set in the iron
core saturation coefficient.
Check the T1 parameters.
Check motor wiring.
Disconnect the motor from the load
End 3
Rated FLA Alm
Rated Current Set Alarm. Motor current during
tuning was greater than the set value.
Check E02.01.
Check T01.04.
NOTE: * Excessive V/f set value, motor iron core saturation coefficient fault, and rated current set alarm are all displayed
after the auto tuning is completed.