IMPULSE•G+ Mini Advanced Instruction Manual - March 2014
3-8
Suggested Circuit Protection Specifications and Wire Size
In order to comply with most safety standards, some circuit protective devices should be used
between the incoming three-phase power supply and the IMPULSE•G+ Mini. These devices can be
thermal, magnetic, or molded-case breakers (MCCB); or “slow-blow” type fuses such as “CCMR”
or “J.”
CAUTION:
The following guidelines are only suggested values. Always conform to local electrical
codes and wiring practices.
Wiring Size (AWG/KCMIL)
Power Circuit Wiring Control Circuit Wiring
Model #
Rated
Current (A)
Input Fuse
Time Delay
Input Fuse
Class
Inverse Time
Molded/Case
Circuit
Breaker
(3)
Applicable
Gauge
(1)
(AWG)
Control
Wiring
(AWG)
Relay
(AWG)
Ground
Copper
(2)
AWG
230VClass
2001-G+M 3 CC 15 18 to 14 18 to 16 18 to 16 14
2003-G+M 5 CC 15 18 to 14 18 to 16 18 to 16 14
2005-G+M 8 CC 15 18 to 14 18 to 16 18 to 16 14
2008-G+M 15 CC 15 14 to 10 18 to 16 18 to 16 12
2011-G+M 20 CC 20 14 to 10 18 to 16 18 to 16 12
2017-G+M 30 CC 35 14 to 10 18 to 16 18 to 16 10
2025-G+M 40 J 50 10 to 6 18 to 16 18 to 16 8
2033-G+M 50 J 70 10 to 6 18 to 16 18 to 16 8
2047-G+M 60 J 90 6 to 4 18 to 16 18 to 16 4
2060-G+M 80 J 110 8 to 2 18 to 16 18 to 16 4
460VClass
4001-G+M 2 CC 15 14 to 10 18 to 16 18 to 16 14
4002-G+M 3 CC 15 14 to 10 18 to 16 18 to 16 14
4003-G+M 6 CC 15 14 to 10 18 to 16 18 to 16 14
4004-G+M 8 CC 15 14 to 10 18 to 16 18 to 16 14
4009-G+M 15 CC 15 14 to 10 18 to 16 18 to 16 12
4014-G+M 25 CC 30 14 to 10 18 to 16 18 to 16 10
4018-G+M 30 CC 40 10 to 6 18 to 16 18 to 16 10
4024-G+M 35 J 50 10 to 6 18 to 16 18 to 16 8
4031-G+M 45 J 60 10 to 6 18 to 16 18 to 16 8
References:
1. NFPA 70 National Electrical Code 2008 Table 610-14(a).
2. NFPA 70 National Electrical Code 2008. Table 250-122.
3. NFPA 70 National Electrical Code 2008. Table 430.52.