IMPULSE•G+ Mini Advanced Instruction Manual – March 2014
5-68
The stall prevention/current limit level during running is set as a percentage of inverter rated current.
A setting of L03.05 = 00 disables current limit during running. During speed agree, if the output
current exceeds this current limit level (L03.06) during running, deceleration starts. When the output
current decreases below this current limit level (L03.06), acceleration starts, up to the set frequency.
See Figure 5-28 below.
Figure 5-28: Stall Prevention/Current Limit During Running
Parameter
Code Name Function Range
Initial
Value
Access
Level
L03.06 Stall Prevention Run
Level
Stall prevention level during
run.
30–150% 150 Basic/Adv