IMPULSE•G+ Mini Advanced Instruction Manual – March 2014
5-24
C05.03 LC Setting Time Sets the time to hold the output frequency
allowing the output current/torque to
stabilize.
0.00–2.55
sec
0.15 Adv
C05.04 LC Testing Time Sets the time (after the LC Setting Time)
for comparing output current/torque to
values for a particular LC Zone being
tested.
0.00–2.55
sec
0.25 Adv
C05.05 LC Acceleration
Margin
Sets the margin for Load Check detection
during acceleration. A setting of 00 is the
most sensitive.
00–50 5 Adv
C05.07 LC Margin Sets the margin for Load Check detection
at speed agree. A setting of 00 is the most
sensitive.
00–20 5 Adv
C05.08 LC Lowering Speed Sets the maximum lowering speed after an
LC alarm.
0.1–30.0 Hz 6.0 Adv
C05.09 LC Zone 01 Current/Torque values detected during LC
set up for Zone 01
000–250% 000 Adv
C05.10 LC Zone 02 Current/Torque values detected during LC
set up for Zone 02
000–250% 000 Adv
C05.11 LC Zone 03 Current/Torque values detected during LC
set up for Zone 03
000–250% 000 Adv
C05.12 LC Zone 04 Current/Torque values detected during LC
set up for Zone 04
000–250% 000 Adv
C05.13 LC Zone 05 Current/Torque values detected during LC
set up for Zone 05
000–250% 000 Adv
C05.14 LC Zone 06 Current/Torque values detected during LC
set up for Zone 06
000–250% 000 Adv
C05.15 LC Zone 07 Current/Torque values detected during LC
set up for Zone 07
000–250% 000 Adv
C05.16 LC Zone 08 Current/Torque values detected during LC
set up for Zone 08
000–250% 000 Adv
C05.17 LC Zone 09 Current/Torque values detected during LC
set up for Zone 09
000–250% 000 Adv
C05.18 LC Zone 10 Current/Torque values detected during LC
set up for Zone 10
000–250% 000 Adv
C05.19 LC Zone 11 Current/Torque values detected during LC
set up for Zone 11
000–250% 000 Adv
C05.20 LC Zone 12 Current/Torque values detected during LC
set up for Zone 12
000–250% 000 Adv
C05.21 LC Zone 13 Current/Torque values detected during LC
set up for Zone 13
000–250% 000 Adv
C05.22 LC Zone 14 Current/Torque value detected during LC
set up for Zone 14
000–250% 000 Adv
C05.23 LC Zone 15 Current/Torque value detected during LC
set up for Zone 15
000–250% 000 Adv
C05.24 LC Zone 16 Current/Torque value detected during LC
set up for Zone 16
000–250% 000 Adv
C05.25 LC Integral Time Integral time used to smooth transitions 0.00–2.55
sec
0.05 Adv
C05.26 LC Delay Time Load Check delay time for transitions 0.00–2.55
sec
0.25 Adv
C05.27 LC Rev Dir Delay Minimum delay between Reverse to
Forward transition after Reverse frequency
exceeds C05.28
0.00–2.55
sec
0.00 Adv
C05.28 LC Rev Dir Freq Minimum frequency that will trigger the
C05.27 delay
0.0–60.0 Hz 30.0 Adv
Parameter
Code Name Function Range Initial Value
Access
Level