106
5 SYSTEM CONFIGURATION
5.4 Structure of CC-Link IE TSN Class B/A Devices (CC-Link IE TSN Protocol Version 1.0 Only) and Ethernet Devices
Coexistence of line and star topologies
Line and star topologies can be mixed according to the availability of connection as described below.
Configure the system with the number of CC-Link IE TSN Class B device stations and industrial switches (for CC-Link IE
TSN Class B) as eight or less in total for each port of the master station on the transmission path from the master station to
the CC-Link IE TSN Class B device of the end.
When connecting CC-Link IE TSN Class A devices, they must be connected to the end side of a CC-Link IE TSN Class B
device or to an industrial switch (for CC-Link IE TSN Class B). In this case, the network can be configured in a star topology
with an industrial switch (for CC-Link IE TSN Class B) or an industrial switch (for CC-Link IE TSN Class A).
No.0: Master station
No.1, No.6: Device station (1st device)
No.3, No.9, and No.11: Device station (8th station)
No.4, No.5, No.7, No.8, and No.10: Device station
Class A: CC-Link IE TSN Class A device
Class B: CC-Link IE TSN Class B device
No.0
Class B
No.1
Class B
No.3
Class B
No.5
Class A
No.4
Class A
...
...
No.7
Class B
No.8
Class B
No.6
Class B
......
No.9
Class B
No.10
Class B
......
No.11
Class B
No.12
Class A
......
No.13
Class A
Industrial switch
(for CC-Link IE TSN Class A)
Industrial switch
(for CC-Link IE TSN Class B)
Industrial switch
(for CC-Link IE TSN Class B)